7. Starting, operation
Electrical connection
WARNING!
Connect the enclosure to ground through the process connection, against electromagnetic
EN
fields and electrostatic discharge.
WARNING!
Specific conditions for safe use in explosive atmosphere:
External earthing connection shall be established by end-user via pressure connection
■
minimum 4 mm² required. External earthing connection shall be corrosion resist and
locked against rotation.
The connector provided by the end user in the end use application shall be in accordance
■
with all applicable clauses of EN/IEC 60079-0, EN/IEC 60079-7 and EN/IEC 60079-15. A
minimum degree of protection IP54 according to EN/IEC 60529 shall be ensured.
Cable provided by end-user shall be suitable for the ambient temperature.
■
The sub-D version has to be installed in a way that it is protected against an impact energy
■
of more than 4 J. The connector as well as the corresponding sealing are provided by the
end user in the end use application and shall be in accordance with all applicable clauses
of EN/ IEC 60079-0, EN/IEC 60079-7 and EN/IEC 60079-15. A minimum degree of protec-
tion IP54 according to EN/IEC 60529 shall be ensured.
The equipment shall only be used in an area with a maximum pollution degree of 2, as
■
defined in EN/IEC 60664-1.
12
WIKA operating instructions, model WU-2x