4-13. Output Peak Current
For 24V, 36V output model, please meet the following conditions. Reduce peak current value according to output
derating as section 6-2.
Input voltage range
Continuous Peak output time (τ)
Peak output current (Ip)
Average DC output current (Im)
Im =
Duty =
4-14. Auxiliary Supply
Auxiliary supply (5V, 0.3A max) is provided to ease customer application. Aux voltage is always available as long as
input power in the specified voltage range is present.
4-15. Output Dynamic Load Response
During output dynamic load test from no load condition, the output voltage level might experience a higher voltage dip
of 15% (typ).
For example, VIN = 230VAC Dynamic Load = 0% - 100% Ta = 25degC, the output voltage level dip will be -15% (typ).
: AC85V~265V
: Within 10 seconds
: Within the rated peak output current
: Within the rated output current, Iav
(Ip-a) x τ
+ a
Iav
T
τ
x100(%)
35(%)
T
Ip
aA
0A
Ip
: Peak output current (A)
Iav
: Rated output current (A)
Im
: Average output current (A)
: Peak current pulse width
τ
(sec)
T
: Period (sec)
10
TDK-Lambda
GWS
Series
500
INSTRUCTION MANUAL
τ
T
Im