4-6. Low Output Detection Circuit (DCOK)
Low output voltage detection circuit is provided. DCOK signal is only valid after AC input is turn-on for more than one
sec. DCOK signal will turn "High" level to indicate abnormal status when the output voltage becomes less than
approximately 80% of rated. It uses the open collector method as shown below
4-7. Remote ON/OFF Control
Remote ON/OFF control is provided.
Using this function, output on/off is allowed to be controlled without input voltage on/off. The output is turned ON when
CNT+ and CNT- terminals are shorted, while the output is turned OFF when these terminals are opened. When this
function is not used, connect CNT+ and CNT- terminals together. The specifications for this function are as follows
(1) TTL compatible.
(2) The maximum input voltage to CNT+ terminal is 12V, and the maximum allowable reverse voltage is -1V.
(3) The source current for CNT+ terminal is 3.5mA.
(4) A switch or a relay or a transistor or a FET can be used as ON/OFF switch.
The /RL option model reverses the logic of the remote ON/OFF function.
Voltage Range between CNT+ and CNT-
2.4 ≤ H ≤ 12.0V or Open
0.0 ≤ L ≤ 0.8V or Short
Output Status
Standard type
/RL option
OFF
ON
ON
OFF