Installing The Outdoor Unit; Installing The Refrigerant Piping - Mitsubishi Electric Mr.SLIM PUZ-ZM KA Série Manuel D'installation

Masquer les pouces Voir aussi pour Mr.SLIM PUZ-ZM KA Série:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 28

3. Installing the outdoor unit

A M10 (3/8") bolt
B Base
C As long as possible.
D Vent
E Set deep in the ground

4. Installing the refrigerant piping

4.1. Precautions for devices that use R32 refrigerant
• Refer to 1.5. for precautions not included below on using air conditioners with
R32 refrigerant.
• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil
applied to the flared sections.
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,
to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses
specified in the table to the below. Make sure the insides of the pipes are clean
and do not contain any harmful contaminants such as sulfuric compounds,
oxidants, debris, or dust.
Always apply no-oxidation brazing when brazing the pipes, otherwise, the
compressor will be damaged.
B
ZM100-140
ZM100-140
600
Min. 50
* When installing a single outdoor unit, the clearance is 15 mm or more.
• Be sure to install the unit in a sturdy, level surface to prevent rattling noises during
(mm)
operation. (Fig. 3-1)
<Foundation specifications>
Foundation bolt
Thickness of concrete
Length of bolt
Weight-bearing capacity
• Make sure that the length of the foundation bolt is within 30 mm of the bottom
surface of the base.
• Secure the base of the unit firmly with four-M10 foundation bolts in sturdy loca-
tions.
Installing the outdoor unit
• Do not block the vent. If the vent is blocked, operation will be hindered and break-
down may result.
• In addition to the unit base, use the installation holes on the back of the unit to
attach wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 × 15
mm or less) and install on site.
Warning:
• The unit must be securely installed on a structure that can sustain its
weight. If the unit is mounted on an unstable structure, it may fall down and
cause damage or injuries.
• The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incor-
rectly installed unit may fall down and cause damage or injuries.
D
*
Min. 500
600
225
225
1050
Fig. 3-1
Warning:
When installing or relocating, or servicing the air conditioner, use only the
specified refrigerant (R32) to charge the refrigerant lines. Do not mix it with
any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high
pressure in the refrigerant line, and may result in an explosion and other haz-
ards.
The use of any refrigerant other than that specified for the system will cause
mechanical failure or system malfunction or unit breakdown. In the worst
case, this could lead to a serious impediment to securing product safety.
Pipe size (mm)
ø6.35 ø9.52 ø12.7 ø15.88 ø19.05 ø22.2 ø25.4 ø28.58
Thickness (mm)
0.8
• Do not use pipes thinner than those specified above.
• Use 1/2 H or H pipes if the diameter is 19.05 mm or larger.
/ Be sure to have appropriate ventilation in order to prevent ignition. Fur-
thermore, be sure to carry out fire prevention measures that there are no
dangerous or flammable objects in the surrounding area.
M10 (3/8")
120 mm
70 mm
320 kg
0.8
0.8
1.0
1.0
1.0
1.0
1.0
7

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Mr.slim puz-zm100kaMr.slim puz-zm125kaMr.slim puz-zm140ka

Table des Matières