Aduro 22.1 Lux:
Distance to flammable material (see illustrations below)
Behind the
Behind stove with
stove
insulated flue pipe
15 cm
*with insulated pipe
If the stove is positioned against a brick wall or other non-flammable material, there are no minimum distance
requirements. To facilitate cleaning and for the best use of the convection air, we recommend that you leave
a distance of approximately 5-10 cm to the wall.
If the wood burning stove is to be placed close to flammable material such as a wooden floor or carpet, it
must be placed on a non-flammable base. The floor plate should extend for at least 30 cm in front of the
wood burning stove and 15 cm on each side measured from the opening of the combustion chamber.
The wood burning stove must be installed on a floor with the adequate load-
bearing capacity. If the existing construction does not meet this requirement,
appropriate adaptation measures must be taken (e.g. a load-distributing plate).
2.2 Pipe connection
The Aduro 22 series leaves the factory with the flue outlet mounted on the top. If you require the flue outlet
on the back, "breake" the two cover plates on top of the back of the stove. Exchange the exhaust connector
(from the top outlet) with the cover plate from the rear outlet. Mount the cover plate from the rear outlet to the
top outlet. The top outlet is finished with the plate that lies in the ashpan. A flue pipe with an internal diameter
of 150 mm should be used for Aduro stoves. The Aduro 22 series is suitable for installation in a shared flue.
Please ensure that all local rules and regulations are complied with, including CE marking of the flue pipe.
Additionally, distance requirements to flammable material for the pipe must be respected.
To the sides
10 cm
45 cm
Above the
Corner
stove
position
17,5*/20 cm
75 cm
Distance to
furniture
90 cm
37