Figure 11 — 120 Volt AC, 20 Amp Duplex Receptacle
Use each outlet to operate 120 Volt, 60 Hz, single phase
loads requiring 2,400 (2.4 kW) watts at 20 Amps of
current.
120/240 Volt AC, 30 Amp Locking
Receptacle
Use a NEMA L14-30 plug with this receptacle. Connect a
4-wire cord set rated for 250 Volts at 30 Amps (or greater)
(Figure 12).You can use the same 4-wire cord if you plan to
run a 120 Volt load.
Figure 12 — 120/240 Volt AC, 30 Amp Receptacle
4-Wire Cord Set
Y (Hot)
NEMA L14-30
This receptacle powers 120/240 Volt AC, 60 Hz, single
phase loads requiring up to 3,600 watts of power at
20 Amps for 120 Volts; 7,000 watts of power (7.0 kW) at
29.2 Amps for 240 Volts.The outlet is protected by a
double pole circuit breaker.
7000EXL Extended Life Generator
240V
120V
120V
W (Neutral)
X (Hot)
Ground (Green)
CAUTION!
Although this outlet is rated for
240 Volt 30 Amp (up to 7.200 watts), the generator
is only rated for 7,000 watts. Powering loads that
exceed the wattage/amperage capacity of the
generator can damage it or cause serious injuries.
240 Volt loads powered through this outlet should
not exceed 29.2 Amps of current draw.
120 Volt AC, 30 Amp Locking
Receptacle
Use a NEMA L5-30 plug with this receptacle. Connect a
3-wire cord set rated for 125 Volts AC at 30 Amps to the
plug (Figure 13).
Figure 13 — 120 Volt AC, 30 Amp, Locking Receptacle
3-Wire Cord Set
Use this receptacle to operate 120 Volt AC, 60 Hz, single
phase loads requiring up to 3,600 watts (3.6 kW) of power
at 30 Amps.The outlet is protected by a double pole circuit
breaker.
12 Volt DC, 10 Amp Receptacle
This connector (identified by the legend "12-VOLT D.C.")
supplies 12 Volts DC at 10 Amps through battery charging
cables for recharging 12 Volt batteries (Figure 14). See
"Charging a Battery" on page 7.
Figure 14 — 12 Volt DC, 10 Amp Receptacle
9
NEMA L5-30
Neutral
120V
Hot
Ground (Green)