Télécharger Imprimer la page

Bradley S19-2000 Série Instructions Pour L'installation Et L'entretien page 2

Robinet thermostatique mélangeur efx 8 avec cabinet facultatif
Masquer les pouces Voir aussi pour S19-2000 Série:

Publicité

Les langues disponibles

Les langues disponibles

Bradley EFX 8 Thermostatic Mixing Valve with Optional Cabinet
Model S19-2000 Series
Table of Contents
Pre-Installation Information ...................................... 2
Valve Installation Instructions................................... 3
Recess-Mounted Cabinet Installation ....................... 4
Surface-Mounted Cabinet Installation ...................... 5
Pre-Installation Information
Overview
Valve: The EFX 8 Thermostatic Mixing Valve (Model S19-2000) is designed for use with face and eye washes.
Model S19-2000EFX is designed for use with S19-292. The valve consists of a liquid-filled thermal motor and
a piston control mechanism with positive shut-off of hot when cold water supply is lost to prevent scalding.
The valve allows cold flow in the event of loss or interruption of the hot water supply or failure of the ther-
mostat. The valve may be mounted in any position.
The maximum inlet temperature of the valve is 180°F (82°C), with a recommended inlet temperature of
120°F–140°F (49°C–60°C). The valve has a maximum operating pressure of 125 PSI (860 kPA).
Cabinet: The optional recess-mounted or surface-mounted cabinet (For use with S19-2000 only) is constructed
of 18-gauge stainless steel with a 16-gauge stainless steel door. The cabinet finish is either stainless steel or
baked white enamel. The optional cabinet window is made of Plexiglass.
Supplies recommended for installation
• lockable shut-off on the outlet if tempered water is supplied to one or more remote showers
• lockable shut-off on the inlets/supplies
• (6) 1/4" wall anchors and fasteners for surface-mounted cabinet
• (4) 1/4" fasteners (and wall anchors, if necessary) for recess-mounted cabinet
• unions on all connections to facilitate removal of valve
Tools required for installation
• 5/32" Allen key key (for temperature adjustment)
Tools required for maintenance/troubleshooting
• blade screwdriver (for stop/check cover screw removal)
• 3/4" wrench (for acorn nut removal)
• 15/16" socket wrench and needle-nose pliers (for piston liner removal)
• 1/2" deep well socket wrench (for piston assembly's upper seat removal)
Bradley Warranty Information
Product warranties may be found under "Product Information" on our website at www.bradleycorp.com
2
5/14/08
Installation and Maintenance Instructions
Recirculation Instructions ......................................... 6
Maintenance........................................................... 7-8
Troubleshooting ..................................................... 8-9
Parts Breakdown and Service Kits.......................... 10
Bradley Corporation • 215-1291 Rev. L; EN 07-903A

Publicité

loading

Ce manuel est également adapté pour:

S19-2000efx sérieS86-066