Safety; Intended Use; Safety Information; Ce Designation - Stiebel Eltron PK 10 Utilisation Et Installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 16

INSTALLATION

SAfeTy

2.
Safety
2.1

Intended use

The appliance may only be used for the pumping of water. The
appliance may only be operated indoors. This appliance may not
be used as a submerged pump or installed in a moist environment.
This appliance is designed for domestic use. It can be used safely
by untrained persons. The appliance can also be used in a non-
domestic environment, e.g. in a small business, as long as it is
used in the same way.
2.2

Safety information

Operate the appliance only when fully installed and with all safety
equipment fitted.
Risk of injury!
The appliance may be used by children aged 8 and
up and persons with reduced physical, sensory or mental
capabilities or a lack of experience provided that they are
supervised or they have been instructed on how to use the
appliance safely and have understood the resulting risks.
Children must never play with the appliance. Children must
never clean the appliance or perform user maintenance unless
they are supervised.
In the event of a malfunction, please consult a qualified contractor.
Safeguard the appliance against frost.
2.3

CE designation

The CE designation shows that the appliance meets all essential
requirements according to the:
— Electromagnetic Compatibility Directive (Council Directive
89/336/EEC)
— Low Voltage Directive (Council Directive 73/23/EEC)
2.4

Test symbols

See type plate, which is located on the top of the appliance.
2.5

Instructions, standards and regulations

Observe all applicable national and regional
regulations and instructions.
3.

Equipment description

3.1

Standard delivery

— Pump with integrated condensate collecting vessel, power
supply cable and alarm connection cable.
— 5 m pressure hose with 10 mm diameter
3.2

Properties

This appliance is for automatically pumping off collected
condensate. This appliance is suitable for use with heat pumps
and ventilation appliances.
— This appliance is only necessary if any condensate arising
cannot be guided to a drain by means of a natural gradient.
PK 10
— This appliance is a monoblock centrifugal pump and has an
overtemperature cut-out with automatic restart once the
temperature has dropped sufficiently.
3.3

Function

The incoming condensate is collected in a collecting vessel. If the
water level exceeds the switching-on point, the pump is switched
on by means of a float. Once the condensate has been siphoned off
to leave only a small residual amount, the pump switches off. An
additional float prevents the collecting vessel from overflowing. On
reaching the alarm activation point, this float activates the alarm
contact. With the alarm contact, a warning lamp or warning sound
can be activated or the connected main appliance switched off.
a
Cut-off point (see "Technical information")
b
Switching-on point
c
Alarm activation point
4.
Installation
4.1

Installation location

Install the appliance in an upright position beneath the condensate
drain of the heat pump or ventilation appliance. The appliance can
be placed on the floor or mounted on the wall.
Ensure that there is sufficient free space around the appliance to
enable the drive motor to remain cool.
4.2

Appliance installation

Ensure that no kinks appear in the condensate pipes. Install a
protective pipe if necessary.
4.2.1 Freestanding
| 11

Publicité

Table des Matières
loading

Table des Matières