Installation Instructions
Determining the Number of Transmitters

Installing Optional Remote Sensors

301IRFS Sensor
The refrigerant sensor should be installed at the recommended height,
which is 30 cm (1 foot) from the floor.
Communication cables should be 2-24
AWG, twisted and shielded (Belden 9841
or equivalent), which should be connected
in a daisy chain from the 301EM (as
shown).
Power cables should be 14 AWG cable,
maximum length of 60 m (200 ft). The first
four sensor power cables may be wired
directly to the 301EM. Additional sensors
require an external power supply (one per
group of four sensors, to a maximum of 20
sensors in total), using the same rated
cable as units wired to the 301EM.
14
301EM User Manual
Power
sensor #5
External
V- (black)
Power
Supply
V+ (red)
sensor #6
HPTV5DC8,
Input: 115 VAC 1A,
Output: 4.0A@6 and
12VDC, 2.5A@
24VDC
sensor #7
sensor #8
From
301EM
A
(white)
B
(green)
Comm.
To next
sensors