Installation Of The Mounting Backplane - Lenze L-force 9400 Instructions De Montage

Masquer les pouces Voir aussi pour L-force 9400:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

2

Installation of the mounting backplane

Note!
The devices must be installed in housings (e.g. control cabinets) to meet
applicable regulations.
How to proceed:
1. Prepare the mounting plate by providing M5 mounting holes in a grid pattern.
2. When footprint filters are used: screw together mounting base and footprint filter.
3. Screw the mounting base or the footprint filter onto the mounting plate.
4. Add further units.
Mounting grid
We recommend to provide the mounting plate with a grid pattern of threaded holes for
attaching the devices. This preparation enables easy attachment of the mounting bases
and filters that may be required. Thus the device sizes I ... III can be mounted directly next
to each other.
Note!
ƒ
ƒ
ƒ
EDK94ASH24 DE/EN/FR/ES/IT 3.0
Installation of the mounting base
M5 screw and washer assemblies or hexagon socket screws with washers
are permitted.
Tightening torque: 3.4 Nm / 30 lb-in.
In the mounting backplane, the screwed connection may not jut out more
than 7 mm.
2
43

Publicité

Table des Matières
loading

Table des Matières