Electrical installation

6.1

Important notes

(
Stop!
Possible overheating of the brake resistor during operation
Inadequate heat dissipation during operation can cause the brake
resistor to overheat.
Possible consequences:
ƒ
ƒ
Protective measures:
ƒ
ƒ
6.2

Connection data

Connection
RB1, RB2
(brake resistor)
PE (PE
conductor)
T1, T2
(thermal
contact)
1)
I
Tip!
The brake resistor has two PE connections, one inside, the other
outside the housing.
ƒ
ƒ
EDKRBG018R DE/EN/FR/ES/IT 8.0
The brake resistor is destroyed.
The drive is not braked but coasts to a standstill.
Always connect the thermal contact of the brake resistor.
Integrate the thermal contact into the overall equipment
monitoring apparatus in such a way that the supply of power to
the standard device is switched off if the brake resistor overheats
(e.g. switch−off by means of mains contactor control).
Cable gland
1)
M25 / M40
M16
ERBG023D05K6, ERBG028D04K1
If you use a brake resistor cable with PE conductor, lead this
through the cable gland and place the PE conductor inside.
If you use a separate PE cable, connect it outside.
l
Electrical installation
Important notes
Connection type
Connection size
Stud terminal
0.75 ... 1.5 mm
Tunnel terminal
18 ... 16 AWG
Starting torque
4 Nm
M6
35.4 lb−in
2
0.32 Nm
2.85 lb−in
6
49