G
®
THERMASGARD
Calibratable room temperature measuring transducer THERMASGARD
with con tinuous output, with or without optional display for displaying the actual temperature
in an elegant enclosure made of plastic, with snap-on lid, base with 4-hole attachment
for installation on vertically or horizontally installed in-wall flush boxes, with predetermined
breaking point for on-wall cable entry, or in enclosure made of stainless steel (top and
bottom part are of stainless steel, the lid is screwed on), vandal-proof version e.g.
for schools, military barracks, and public buildings. This room temperature transmitter ⁄
residential room temperature sensor is used to detect ⁄ display temperatures in closed dry
rooms, in apartments, in offices, supermarkets and business facilities.
TECHNICAL DATA
Power supply:
Power consumption:
Sensor:
Measuring ranges:
Output:
Ambient temperature:
Connection type:
Process connection:
Enclosure:
Dimensions:
Electrical connection:
Installation:
Humidity:
Protection class:
Protection type:
Standards:
Optional:
THERMASGARD
®
RTM 1 – Room temperature measuring transducers
Type ⁄ WG01
RTM1 - U
R T M1- U
R T M1- U _ D I S P L AY
R T M1- U E
RTM1 - I
R T M1- I
R T M1- I _ D I S P L AY
R T M1- I E
Extra charge:
RTM
24 V AC ⁄ DC ± 10 % for output 0 - 10 V
15 - 36 V DC for output 4...20 mA
(depending on working resistance)
< 1.0 VA ⁄ 24 V DC
< 2.2 VA ⁄ 24 V AC
Pt1000, DIN EN 60751, class B
multi-range switching
with 8 switchable measuring ranges,
see table (other ranges optional)
operating range –30...+70 °C
with manual zero point correction (± 10 K)
0 - 10 V or 4...20 mA
measuring transducer –30...+70 °C
2- or 3-wire connection
by screws
plastic, material ABS, colour pure white (similar to RAL 9010),
(optional stainless steel)
85 x 85 x 27 mm (Baldur 1)
75 x 75 x 25 mm (stainless steel)
0.14 - 1.5 mm² via terminal screws
wall mounting or on in-wall flush box Ø 55 mm, base with 4-hole
for mounting on vertically or horizontally installed in-wall flush boxes
for cable entry from the back, with predetermined breaking point
for on-wall cable entry from top ⁄ bottom in case of plain on-wall installation
< 95 % r. H., non-precipitating air
III (according to EN 60 730)
IP 30 (according to EN 60 529)
CE conformity, electromagnetic compatibility
according to EN 61326, according to EMC directive 2004 ⁄ 108 ⁄ EC
Two-line display with illumination, cutout 36 x 14 mm (W x H),
for displaying the ACTUAL temperature and the internal diagnostics
(sensor breakage, sensor short circuit)
Sensor
Output
Pt1000
0 - 10 V
Pt1000
0 - 10 V
Pt1000
0 - 10 V
Pt1000
4...20 mA
Pt1000
4...20 mA
Pt1000
4...20 mA
Other ranges optional
®
RTM 1
Display
Features
Display
–
Display
Stainless steel enclosure
–
Display
Stainless steel enclosure
Rev. 2016 - V20 GB
Standard
Sensor
breakage
Sensor
short circuit
Item No.
IP 30, U - variant
1101-41A1-0000-200
■
1101-41A1-2000-200
1101- 4151- 0000-200
IP 30, I - variant
1101-41A2-0000-200
■
1101-41A2-2000-200
1101- 4152- 0000-200