Lamborghini Caloreclima Reply 51 Instructions D'utilisation, D'installation Et D'entretien page 72

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Connection with separate pipes
Separate Ø80 ducts can be connected directly to the unit. Insert the seal 1KWMA84A on the Ø80 pipes leaving the unit
and make it adhere to the upper wall of the cabinet.
Before proceeding with installation, make sure the maximum permissible length has not been exceeded, by means of
a simple calculation:
1. Establish the layout of the system of split flues, including accessories and outlet terminals for each of the two burner/
exchanger bodies.
2. Consult the table 3 and identify the losses in meq (equivalent metres) of every component, according to the instal-
lation position.
3. Check that the sum total of losses is less than or equal to the maximum permissible length in table 2.
Table. 2 - Max. length separate ducts
Max. permissible length
Table. 3 - Accessories
Ø 80
PIPE SECTION
TERMINAL
Direct connection of terminals Ø 80 code 041013X0
Each single module can be connected directly to the terminal kits 041013X0 as given in , even with connection in bank
fig. 29.
Each kit comprises a Ø80 terminal with grille (ref. 3), a seal (ref. 1) and a centering ring (ref. 2). For models Reply 71/
i-101/i use 2 kits per module, and 1 kit for models Reply 51/i.
3
1
2
72
PIPE
1 m M/F
BEND
45° M/F
90° M/F
with test point
fumes, wall with antiwind
FLUE
Split air/fumes 80/80
cod. 3540H322 - 09/2008 (Rev. 01)
Reply 51 - 71 - 101
Separate ducts
For each single Exchanger/Burner Body
20 m
1KWMA83W
1KWMA65W
1KWMA01W
1KWMA70W
1KWMA86A
1KWMA84U
fig. 29
eq
Losses in m
eq
Fume exhaust
Vertical
Horizontal
1.6
2.0
1.8
2.0
0.3
5.0
5.0
EN

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Reply 71Reply 101

Table des Matières