The maintenance-free microprocessor-controlled room sensor AERASGARD
quality based on a mixed gas sensor / VOC sensor. The measurement value is converted into standard signal of 0 -10 V.
The maintenance-free microprocessor-controlled room sensor AERASGARD
is used for determining the air quality based on a mixed gas sensor / VOC sensor. The measurement value is converted into standard signal of 0 -10 V or
4...20 mA. Optional with traffic light indicator (five coloured LEDs).
Elegant enclosure made of plastic, with snap-on lid, base with 4-hole attachment, for installation on vertically or horizontally installed flush-mounted
boxes, with predetermined breaking point for surface-mounted connection or in enclosure made of stainless steel (top and bottom parts are stainless
steel, the cover is screwed on), vandal-proof version e.g. for schools, barracks and public buildings.
It is used
- For air quality measurement in offices, hotels, meeting rooms and convention centres, apartments, stores, and restaurants, etc.
- For quantitative evaluation of room air pollution with contaminating gases (cigarette smoke, body perspiration, exhaled breathing air, solvent vapours,
emissions from building members and cleaning agents)
- For adjustable sensitivity regarding the maximum air contamination to be expected
- For room ventilation as-needed, enabled by air changes only taking place when air is polluted while conserving energy at the same time.
The sensor's service life depends on the type of burden and gas concentration and is more than 60 months under normal load conditions. The new design
allows you to choose between three sensitivity ranges that are adjusted using DIP switches, giving you three measuring ranges: LOW for low, MEDIUM
(default) for medium, and HIGH for high VOC sensitivity. VOC is the abbreviation for volatile organic compounds. According to the definition by the World
Health Organization WHO, VOC are organic substances with a boiling range from +60 to +250 °C. Examples of VOCs include compounds of the substance
groups alkanes ⁄ alkenes, aromatic compounds, terpenes, halogenated hydrocarbons, esters, aldehydes, and ketones. There is a large number of naturally
occurring VOCs, some of which are also released into the atmosphere in substantial quantities, e.g. terpenes and isoprene from forests.
TECHNICAL DATA
Power supply:
Power consumption:
Sensor:
Measuring range:
Output:
Relay output:
Measuring accuracy:
Service life:
Gas exchange:
Warm-up time:
Ambient temperature:
Response time:
Electrical connection:
Enclosure:
Dimensions:
Installation:
Protection class:
Protection type:
Standards:
Optional:
®
AERASGARD
RLQ - SD – Room air quality sensor (VOC) and measuring transducer, Standard
®
AERASGARD
RLQ - W – Room air quality sensor (VOC) and measuring transducer, Premium
Type ⁄ WG02
Measuring Range
VOC
RLQ - SD
R L Q - S D - U
0...100 %
RLQ - W
R L Q -W
0...100 %
R L Q -W VA
0...100 %
R L Q -W- A
0...100 %
A = with "traffic light" (five coloured LEDs) for displaying the air quality (VOC).
Note:
This unit must not be used as safety-relevant device!
24 V AC ⁄ DC (± 10 %)
< 1.5 W ⁄ 24 V DC typical; < 2.9 VA ⁄ 24 V AC typical; peak current 200 mA
VOC sensor (metal oxide) (VOC = volatile organic compounds)
with manual calibration (via zero button),
RLQ - SD with automatic calibration (fixed)
RLQ -W
with automatic calibration (can be deactivated via DIP switches)
0...100 % air quality; referred to calibrating gas;
multi-range switching (selectable via DIP switches) VOC sensibility low, medium, high
(0 V = clean air, 10 V = polluted air)
RLQ - SD 0 -10 V (fixed)
RLQ - W
0 -10 V or 4...20 mA, working resistance < 800 Ω (selectable via DIP switches)
with offset potentiometer (± 10 % of the measuring range)
RLQ - SD without changeover contact
RLQ - W
with potential-free changeover contact 24 V (switchpoint can be adjusted from 0...100 % of the output signal)
± 20 % of final value (referred to calibrating gas)
> 60 months
by diffusion
approx. 1 hour
0...+ 50 °C
approx. 1 minute
2
0.14 - 1.5 mm
, via screw terminals
plastic, material ABS, colour pure white (similar to RAL 9010), stainless steel enclosure optional
85 x 85 x 27 mm (Baldur 1) / 100 x 100 x 25 mm (stainless steel)
wall mounting or on in-wall flush box, Ø 55 mm, base with 4-hole for mounting on vertically or horizontally
installed in-wall flush boxes for cable entry from the back, with predetermined breaking point for on-wall cable entry
from top ⁄ bottom in case of plain on-wall installation
III (according to EN 60 730)
IP 30 (according to EN 60 529)
CE conformity, electromagnetic compatibility according to EN 61 326, EMC Directive 2014 ⁄ 30 ⁄ EU,
Low Voltage Directive 2014 ⁄ 35 ⁄ EU
with traffic light indicator (five coloured LEDs, see table) for displaying the air quality.
Output
VOC
(fixed)
0 -10 V
(switchable)
0 -10 V ⁄ 4...20 mA
0 -10 V ⁄ 4...20 mA
0 -10 V ⁄ 4...20 mA
®
RLQ - SD with automatic calibration (fixed) is used for determining the air
®
RLQ - W with automatic calibration (can be deactivated via DIP switches)
Features
–
Changeover contact
Changeover contact, stainless steel enclosure
Changeover contact, LEDs
Rev. 2018 - V33 GB
Item No.
1501-61C0-1001-200
1501-61C0-7301-200
1501-61C0-7301-205
1501-61C0-7331-200