1.
Safety instructions
For skilled electricians and trained
personnel in accordance with national
legislation, including the relevant
standards and, where applicable, in acc.
with IEC/EN 60079-14 on electrical
apparatus for explosive atmospheres.
– The light fitting must not be operated in
zone 0 or zone 20 hazardous areas!
– The light fitting must not be use while
excessive deposit of dust
( accd. IEC/EN 60079-31) exist.
– The technical data indicated on the light
fitting are to be observed!
– Changes of the design and modifica-
tions to the light fitting are not
permitted!
– The light fitting shall be operated as
intended and only in an undamaged and
perfect condition!
– Only genuine Zumtobel spare parts may
be used for replacement!
– Repairs that affect the explosion
protection, may only be carried out by
Zumtobel or a qualified "electrician"!
– These operating instructions shall not
be kept inside the light fitting during
operation!
The national safety rules and regulations
for prevention of accidents and the
following safety instructions which are
marked with an ( ) in these operating
instructions have to be considered!
10
Explosion protected emergency light fittings
Series: KXA-2 2600 NE, KXA-2 5100 NE
2.
Technical data
Type examination certificate:
Marking acc. to 2014/34/EU and standard:
EN 60079-0
gas
dust
Rated voltage AC ± 10 %
Rated frequency range:
cos p
Version
Rated current
120 V AC/DC
230 V AC/DC
254 V AC/DC
Rated power
Emergency operation time
Luminous flux factor (emerg. light)
related to 1 LED row in rated
operation:
Immunity from interference to IEC/EN 61000-6-2: fulfilled
Emission of interferences to IEC/EN 61000-6-4:
Insulation class to IEC/EN 61140
Degree of protection IEC/EN 60529
(1)
Perm. ambient temperature
KXA-2 .... NE
apecitied
Storage temperature in original packing
Supply terminal clamping capacity
2 x per terminal
min.
max.
Conductor cross-section with through-wiring
Ex-e cable entry
Standard version
suitable cables and test torques of the pressure
screw
min.
1 2
3
Seal 1+2+3
max.
Seal 1+2
min.
1 2
3
max.
Seal 1
min.
1 2
3
max.
Metal
Test torque for screw in thread cable entry:
Test torque for breathing plug M25 x 1,5:
(1)
Intensive sun radiation in areas of high ambient temperatures may cause inadmissible temperature rise inside
of the luminaire. This may result a decrease in lifetime of the electronic ballast (EVG). Therefore those luminaires
should be switched off during daytime by a photocell control.
(2)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance work
on the cable entry.
BVS 10 ATEX E 154
II 2 G Ex db eb mb ib op is IIC T4 Gb
II 2 D Ex tb IIIC T80 °C Db
120 V to 254 V
50 to 60 Hz
> 0.95
KXA-2 2600 NE
0.40
0.20
0.18
45 VA
1.5 h
3.0 h (see wiring diagram)
KXA-2 2600 NE
at 1.5 h
ca. 95 %
at 3.0 h
ca. 65 %
fulfilled
I
IP66 / IP67
-25 °C ... +45 °C
-5 °C ... +35 °C
-25 °C ... +45 °C
single-wire
1.5 mm²
6.0 mm²
2.5 mm² for max. 16 A
M25 x 1.5
Ø
8.0
(2)
10.0
10.0
(2)
13.0
13.5
(2)
17 .5
M20 x 1.5 thread
3.0 Nm
3.0 Nm
GB
KXA-2 5100 NE
0.60
0.35
0.30
70 VA
KXA-2 5100 NE
ca. 65 %
ca. 45 %
multi-wire
1.5 mm²
6.0 mm²
Nm
1.5
2.0
2.3
2.6
1.3
2.3