DIRIS A40 /A41
CARACTÉRISTIQUES TECHNIQUES
TECHNICAL CHARACTERISTICS - TECHNISCHE DATEN -
CARATTERISTICHE TECNICHE - TECHNISCHE EIGENSCHAPPEN -
CARACTERÍSTICAS TÉCNICAS - CARACTERÍSTICAS TÉCNICAS
GB
CASE
Dimensions:
Connection:
IP index:
Weight:
DISPLAY
Type :
MEASUREMENTS
Three-phase (3 or 4 wires), two-phase (2 wire) and single-phase networks
VOLTAGE (TRMS)
Direct measurement:
Measurement via PT:
Display and resolution
Permanent overload:
Update period:
CURRENT (TRMS)
Via CT with:
Minimum measuring current
Input consumption:
Display:
permanent overload:
intermittent overload:
Update period:
Maximum ratio KI x KU:
POWER
Total:
Update period:
FREQUENCY
Update period:
ENERGY / MEASUREMENT ACCURACY
Current:
Voltage:
Power:
Power factor:
Frequency:
Active energy metering:
Reactive energy metering:
AUXILIARY SUPPLY IEC / CE
110 to 400 V AC 50/60 Hz
120 to 350 V DC
12 to 48 V DC
Consumption:
52
96 x 96 x 60 mm
or 96 x 96 x 80 mm with all optional modules (DIN 43700)
via 2.5 mm
2
disconnectable terminals
(voltage and others) and 6 mm
IP52 (front panel) and IP30 (case)
400 gr.
Backlit LCD display
from 18 to 700 V AC (phase/phase)
from 11 to 404 V AC (phase/neutral)
• Primary:
up to 500 kV
• Secondary:
60, 100, 110, 115, 120, 173 and 190 V AC
from 0 to 500.0 kV
760 V AC
1 second
• Primary:
up to 10000 A
• Secondary:
1 or 5 A
10 mA
< 0.3 VA
from 0 to 11 kA (1.1 times the primary value)
10 A
10 In / 1 second
1 second
10 000 000
0 to 8000 MW/Mvar/MVA
1 second
from 45,0 to 65,0 Hz
1 second
0.2 % from 10 to 110 % / In
0.2 % from 140 to 700 V AC
0.5 % of full scale (-90° à + 90°)
0.5 % for 0.5 < FP < 1
0.1 % from 45 to 65 Hz
± 0.5 % from 0.02 to 1,2 In with PF = 0.5 L or 0.8 C
(class 0.5S IEC 62053-22)
± 2% from 0.1 to 1,2 In with sinϕ = 0.5 L or C
(class 2 IEC 62053-23)
± 10 %
± 20 %
-6 % / + 20 %
< 10 VA
2
fixed terminals (current)
SOCOMEC - Réf. : 876 583 C