2

Safety instructions

The explosion-protected
enclosures and distributions are
not suited for use in
Zone 0.
The electrical connection of enclosures
and distributions may only be carried out
by elektronik specialists acc to EN 60079-14.
Even after disconnection, due to the
battery, the built-in components of the
emergency pack can still be live.
Modifications or design changes to
apparatus and distributions that affect
the explosion protection are not
permitted.
They shall be used for their intended
purpose and shall be in a perfect and
clean state.
Prior to being put into operation, the
boxes shall be checked in accordance
with the instructions as per section 6.
Before initial operation, any foreign
matter shall be removed from the
apparatus.
The national safety rules and regulations
for the prevention of accidents, as well as
the safety instructions included in these
operating instructions, that, like this text,
are set in italics, shall be observed!
2.2

Legend

Safety warning
Note
i
Information
Cooper Crouse-Hinds GmbH
8 8 8 8 8
1

Technical data

1.1
Emergency Pack type GHG 664 5..
Apparatus marking acc. to 94/9/EC:
Explosion category::
EC-type examination certificate:
Rated voltage order no. GHG 660 19..R...1:
Rated voltage order no. GHG 660 19..R...2:
Rated power
Rated operating time
Cross section:
Perm. ambient temperatur:
Perm. storage temperature in original packing:
original packing, dry, in a closed rooms
Degree of protection to EN/IEC 60529:
Insulation class acc. to EN/IEC 61140:
Cable entries
Test torques:
fixing screws:
Cross section:
cable entries:
M20 for armour cables
M25
Wight:
Enclosure material:
Flameproof enclosure:
Terminal and bus bar boxes
Enclosure surface finish:
Colour of enclosure (standard version):
Emergency lighting battery
*
max. permissable tolerances accd. IEC/EN 60079-0: ± 10 %
3

Conformity with standards

The explosion-protected emergency pack
has been developed, manufactured and
tested by Cooper Crouse-Hinds (hereinafter
referred to as CCH
CCH
CCH
CCH) in accordance with DIN
CCH
EN ISO 9001.
The apparat is conform to the standards
specified in the EC-Declaration of conformity,
enclosed separately.
94/9/ EC: Equipment and protective systems
intended for use in potentially explosive
atmospheres.
The Emergency pack fulfil further
requirements, such as the EC directive on
electromagnetic compatibility (2004/108/EG)
II 2 G;
Ex de II C T6
PTB 07 ATEX 2002 X
220 V up to 240 V 50 / 60 Hz
120 V 60 Hz*
max. 80 VA
1,5 h
max 6 mm²
-5° C to +40° C
+5° C to +40° C
IP 66
I
M20
6 mm -12 mm for armour cables
M25
12,5 mm -18 mm
M12
54 Nm
M20
230 Nm
UK 3 (bis 2,5 mm²) 0,6 Nm
UK 5 (bis 4,0 mm²) 0,6 Nm
UK 6 (bis 6,0 mm²) 1,5 Nm
Screw-in thread
11,5 Nm
18,0 Nm
ca.
48 kg
Aluminium alloy pressure casting
Sheet steel
Plastic powder coating
RAL 7032, (enclosure cover- RAL 7022)
Lead battery 2x 12 V / 12 Ah
4

Field of application

The Emergency packs are intended for use
in potentially explosive atmospheres in zones
1,2 in accordance with EN 60079-10!
The enclosure materials used, including any
external metal parts, are high quality
materials that ensure a corrosion resistance
and resistance to chemical substances
according to the requirements for use in a
"normal industrial atmosphere":
- stainless steel AISI 316 L
- aluminium alloy pressure casting
Optionally, a surface protection for tropical
and sea climates, etc. is also available for
use in extremely aggressive atmospheres.
Pressure screw
22,0 Nm
25,0 Nm