Technical data
Type
Power supply
Nominal current
Nominal force
Nominal locking force
Lifetime
Duty cycle
Housing
Ingress protection
Temperature range
Fire stability
Emission sound pressure
level
Nominal stroke length*
Additional functions *
* programmable with software SCS
Normal operation =
SHEV- fast running =
Forces
DXD 150-BSY+ (-HS) DXD 300-BSY+ (-HS)
OPEN
1500 N
CR III
1000 N
CR II
1000 N
CR I
800 N
Closing edge protection
In "CLOSE" direction the drive has an active
protection for the main closing edge. With an
overload in the closing range 3 and 2 the drive runs
"OPEN" for 10 seconds, then drive "CLOSE" again. If
after three attempts a closing is not possible, the
drive remains in this position.
In addition, the drive has a passive clamping
protection. The closing speed in closure Range 2
and 1 is reduced to 5 mm/s.
Higher forces can occur on besides
closing edges. Danger of violent
pressure in handaccessible area.
99.824.27 1.4/05/18
DXD 150-BSY+
DXD 150-BSY+ HS
24 V DC, ±15 %
24 V DC, ±15 %
1,4 A
2,5 A
1500 N
1500 N
1100 N
>20 000 double strokes
30 % (with cycle time 10 minutes)
aluminium powder-coated / polycarbonate
IP 64 ("-W" = IP 54)
-5 ... +75 °C
30 min / 300 °C
LpA ≤ 70 dB(A)
see type plate
closing edge protection activated (3 stroke repeatings)
3000 N
2000 N
All forces
1600 N
+ app. 20 %
800 N
switch-off reserve (temporary)
English
DXD 300-BSY+
24 V DC, ±15 %
2,5 A
3000 N
2200 N
Running speed and forces
depending on magnet position
main closing edge
DXD 300-BSY+ HS
24 V DC, ±15 %
5,0 A
3000 N
7/16
DXD-BSY+ (-HS)