LoRaWAN 863-870 PULSE - Guide utilisateur / User guide version V3.0.0
S322
1
FR
EN
S323
4
S324
4
S325
2
S326
2
S327
2
S328
2
S329
2
Anti-bounce filter period
(pulse minimum width)
(channels A and B)
Current value of meter -
channel A
Current value of meter -
channel B
Flow calculation period
(channels A and B)
Flow threshold (channel
A)
Flow threshold (channel
B)
Leak threshold (channel
A)
Leak threshold (channel
B)
Hexadec-
Default value: 0x22
imal
Bits 0 to 3 : anti-bounce filter period - channel A
•
Value 0: deactivated
•
Value 1: 1 ms
•
Value 2: 10 ms
•
Value 3: 20 ms
•
Value 4: 50 ms
•
Value 5: 100 ms
•
Value 6: 200 ms
•
Value 7: 500 ms
•
Value 8: 1 s
•
Value 9: 2 s
•
Value A: 5 s
•
Value B: 10 s
•
Value C à F : reserved
Bits 4 to 7 : anti-bounce filter period - channel B
•
Value 0: deactivated
•
Value 1: 1 ms
•
Value 2: 10 ms
•
Value 3: 20 ms
•
Value 4: 50 ms
•
Value 5: 100 ms
•
Value 6: 200 ms
•
Value 7: 500 ms
•
Value 8: 1 s
•
Value 9: 2 s
•
Value A: 5 s
•
Value B: 10 s
•
Value C à F : reserved
Decimal
Default value: 0
Min/max : 0 to (2
Unit : number of pulses
In COMMAND mode, it is possible to write a new
value in this register (for example an initialization
value, an adjustment value ...).
Decimal
Default value: 0
Min/max : 0 to (2
Unit : number of pulses
In COMMAND mode, it is possible to write a new
value in this register (for example an initialization
value, an adjustment value ...).
Decimal
Default value: 60
Min/max : 1 to 1440
Unit :minute
Decimal
Default value :0 (deactivated)
Min/max : 0 to 65535
Unit: pulses per hour
Decimal
Default value :0 (deactivated)
Min/max : 0 to 65535
Unit: pulses per hour
Decimal
Default value: 0
Min/max : 0 to 65535
Unit : pulses per hour
Decimal
Default value: 0
Min/max : 0 to 65535
Unit : pulses per hour
)
32-1
)
32-1
Page
78