Periodic transmission with history

The product allows the accumulation of several successive meter values before the periodic transmis-
sion of the set of values according to the following scheme:
No
No
The parameters associated with this mode of operation are:
Enabling and Configuring inputs (register 320)
Historisation period (register S321)
Sending frequency (S301)
Anti-bounce timer period (registers S322)
A complete list of the registers can be found in paragraph 3.4.
Eg:
Register
Value encoding
S320
Hexadecimal
S301
Decimal
S321
Decimal
S322
Hexadecimal
Product in
standby
Historical
period
reached
?
Yes
Number
of record-
ed values
reached?
Yes
Sending according to channel activation:
Send frame 0x48
Detected and
validated
pulse
?
Yes
Counting
of the impulse
5A frame for channel A
5B frame for channel B
Value
Result
0x39
Channel A :
Activated
Meter other than gas
Tamper input activated
Channel B :
Activated
Gas meter
Tamper input disabled
4
Sending every 4 historisations (saving)
300
Historisation of the data every 10 minutes
(300x2 seconds=600 seconds).
0x57
Anti-rebound :
Channel A = 500ms
Channel B = 100ms
No
Page
FR
EN
67
of 103