CONTROL MOTORS MOVEMENT
E
Using this function you can verify the direction of motors during closing.
N
If motors opening, invert connection wires on terminals V and W, leaving wire U
G
unchanged.
L
I
LED on
S
2s
H
N.B. Safety devices and flasher unit are not enabled during this mode.
During this function, only the dead man closing control may be used by means of
pushbutton K.
4°
EXECUTE THE TIME MEMORISATION
SINGLE MOTOR SETTINGS (EURO11)
CARRY OUT WITH GATE CLOSED!
N.B. In the event of errors during the pushbutton operation procedure, repeat the
operation after resetting by wiring in Jumper S3 for 1 second and then removing.
LED on
2s
Time setting with 1 motor with or without limit switches
N.B. Limit switches, if connected, stop the motor but do not affect time count. Therefore
when the connected motor is shut down by means of the limit switch, press S1 after 1
second to stop the time count.
If a safety device trips during setting procedures, the gate stops. Activate the "Installer
function" to return the gate to the fully closed position and repeat the saving procedure.
TIME SETTINGS WITH TWO SWING GATE MOTORS - dip 7 ON (EURO22)
LED on
The LED remains permanently lit
2s
Time settings with 2 motors with electric lock and with or without limit switches
N.B. Limit switches, if connected, stop the motor but do not affect time count. Therefore
when the connected motor is shut down by means of the limit switch, press S1 after 1
second to stop the time count.
Opening delay is set at 1.5 seconds.
If a safety device trips during setting procedures, the gate stops. Activate the "Installer
function" to return the gate to the fully closed position and repeat the saving procedure.
The LED remains permanently lit
During the above, if pushbutton K
is pressed, the user can activate
closing by the motor/s to return the
gate leafs to the fully closed
position.
The LED remains permanently lit
SETTINGS FOR TWO SLIDING GATE MOTORS - dip 7 OFF (EURO22)
LED on
2s
LED off
Time settings with 2 motors without electric lock and with or without limit switches
N.B. Limit switches, if connected, stop the motor but do not affect time count. Therefore
when the connected motor is shut down by means of the limit switch, press S1 after 1
second to stop the time count.
No delay function is available on opening.
If a safety device trips during setting procedures, the gate stops. Activate the "Installer
function" to return the gate to the fully closed position and repeat the saving procedure.
This function is useful at peak times when traffic slows down (e.g. entry/exit of employees,
emergencies in residential zones or parking/waiting for removals).
Connect a switch and/or daily/weekly type timer (in place of an N.O. pushbutton) between
common (8) and single pulse input (K) to enable barrier opening and keep the barrier open
LED off
while the switch is turned on or while the timer is activated.
All control functions are inhibited while the barrier is open.
When the switch is turned off, or when the set time has elapsed, controls are re-enabled
and barrier closing is possible.
If microswitch 9 is set to ON (enable standby time before automatic closing), the barrier
closes automatically when the switch is turned off or the set time has elapsed.
LED off
The LED remains permanently lit
OPENING WITH FUNCTION BLOCK
BY MEANS OF SWITCH OR TIMER.
APPLICATION
LED off