11.00/22.00 V to 11.70/23.40 V(SOC1), 11.12/22.24 V to 11.76/23.52 V(SOC2),
11.25/22.50 V to 11.83/23.63 V(SOC3), 11.38/22.72 V to 11.89/23.78 V(SOC4),
11.51/23.02 V to 11.96/23.92 V(SOC5), 11.64/23.28 V to 12.02/24.04 V(SOC6).
•
Voltage controlled (LVD): Disconnects at a fixed voltage between 11.0/22.0 V and 11.9/23.8 V (voltage steps 0.1/0.2 V).
Note: Battery voltage must be below adjusted setting for longer than 2 minutes before LVD occurs.
Note: Voltage levels before/after the slash are valid for 12 V and 24 V systems respectively (valid for the charge controllers presented in this manual).
Factory Settings
You can configure CIS-N-MPPT-LED 85/15 charge controllers via the Remote Control Unit (CIS-CU). See CIS-CU manual for details.
Load mode
Low voltage disconnect
Battery type
Nightlight level
Load 1 evening hours
Load 1 morning hours
Dimming evening hours
Dimming morning hours
Dimming value
(1) PV panel open circuit voltage: Day level = Night level + 1.5/3.0 V