3.0 CONNECTIONS

End of line R*
LINE IN +
LINE IN -
LINE OUT +
LINE OUT -
EOL
+ 24V -
+ FLASH -
SPEAKER
R*: Resistance value must be as indicated in used fire control panel technical manual.
Positive input rest pin for alarm line (output siren) from either fire
detection control panel or other cascaded sirens/bells.
Negative input rest pin for alarm line (output siren) from either fire
detection control panel or other cascaded sirens/bells.
Positive output for alarm line (output siren) to drive any other cascaded
devices.
Negative output for alarm line (output siren) to drive any other
cascaded devices.
End Of Line. Termination for end of line resistance, to be connected to
alarm negative pole from either fire detection control panel or other
sirens/bells just on last device (see example).
Device power supply input (to be taken out of control panel).
Caution: lack of power supply causes the relay to break loose with
consequent opening of end of line resistance R.
Filament flash-lamp connection.
Horn connection.
16/28
HPA700F