INSTALLATION
WARNING: before carrying out any
work, make sure the power supply is
unplugged.
WARNING: electrical wiring, installa-
tion of the fan coils and relevant acces-
sories should be performed by a techni-
cian who has the necessary technical
and professional expertise to install,
modify, extend and maintain systems
and who is able to check the systems
for the purposes of safety and correct
operation.
In the specific case of electrical connec-
tions, the following must be checked:
- Measurement of the electrical system
insulation strength.
- Continuity test of the protection wires.
Instructions essential for the proper
installation of the equipment are shown
here.
The completion of all the operations in
accordance with the specific require-
ments is however left to the experience
of the installation engineer.
The command device is made up of an
electronic control panel, to be flush-
mounted in the wall in a standardised,
3-module rectangular box (type 503).
The control panel is equipped with a
white cover plate.
During the installation phase, it is pos-
sible to choose thermostat-controlled
ventilation or continuous ventilation. The
thermostat is set for thermostat-control-
led ventilation. To set continuous ven-
tilation, it is necessary to remove the
Jumper on the electronic card (see pic-

WIRING DIAGRAMS

READING KEY
IG
= Main switch
M
= Terminal board
MS* = Microswitch
MV = Fan motor
PE
= Earth connection
RX
= Electric heater
VC
= Three way valves (heat)
VCF = Three way valves (heat/cool)
VF
= Three way valves (cool)
A l l
w i r i n g
d i a g r a m s
ture). Avoid installing the control panel
in places directly exposed to the rays
of the sun, draughts, heat sources and
fan coil flow. Install at a height of about
150cm from the floor, on an internal, air-
conditioned wall.
Connect the wires to the control board
as indicated in the electrical layouts.
Use wires with a maximum length of 6
metres.
a r e
c o n s t a n t l y
u p d a t e d .
= On-site wiring
= Optional components
= Components not supplied
VCF
FAN COIL
VF
VC
120VAC 60Hz
Min.
L N
Med.
Max.
P l e a s e
r e f e r
t o
F C X / F C S
FMT10
t h e
o n e s
s u p p l i e d
w i t h
t h e
u n i t .
9