ero electronic ELK Manuel Utilisateur page 38

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Mnemonic
HYST.C
COOLING HYSTERESIS sets the difference in PV units between output
2 turning off and turning on.
Only shown if channel 2 control action is On/Off.
D.BAND
CHANNEL 2 DEADBAND adjusts a zone between heating and cooling
outputs when neither output is on. Off = no deadband. 100 = heating
and cooling off.
MTR.T
MOTOR TRAVEL TIME. This parameter only applies if the controller is
a motorised valve positioner. Set this value to the time that it takes for
the motor to travel from its fully closed to its fully open position.
Note: In motorised valve control only the PB and TI parameters are
active – see below. The TD parameter has no effect on the control.
The next nine parameters are only shown if the timer is configured
SS.SP
SOFT START SETPOINT sets the threshold below which the power is
limited – applies to timer type Soft Start only
SS.PWR
SOFT START POWER LIMIT Sets the power limit during start up –
applies to timer type Soft Start only
DWELL
SET TIME DURATION This parameter only appears if 'TM.CFG' is set
to Dwell, Delayed Start or Soft Start type. It can be adjusted while the
timer is running.
T.ELAP
ELAPSED TIME Time from when RUN was initiated – applies to all
timer types.
36
Scrolling Display and description
0.1 to 200.0 display units
Default 1.0
OFF or 0.1 to 100.0% of
the cooling proportional
band
0.0 to 999.9 seconds
Between SP.HI and SP.LO
-100 to 100%
0:00 to 99.59 hh:mm: or
mm:ss
0:00 to 99.59 hh:mm: or
mm:ss
Part number HA028438. Issue 3.0.
Range
Oct-05

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Etk

Table des Matières