Style 2: Direct wire strain relief
Remove the knockout as needed for the flexible conduit
connection.
Assemble a UL listed conduit connector in the opening.
A. Removable retaining nut
B. Strain relief
Feed the flexible conduit behind the black horizontal
cross brace and through the strain relief, allowing enough
slack to easily attach the wiring to the terminal block.
A. Black horizontal cross brace
B. Flexible conduit
Tighten strain relief screw against the flexible conduit.
14
A
B
A
B
4. Complete installation following instructions for your type of
electrical connection:
4-wire (recommended)
3-wire (if 4-wire is not available)
Electrical Connection Options
If your home has:
And you will be
connecting to:
4-wire receptacle
A UL listed,
(NEMA type 14-50R)
250-volt
minimum,
40-amp, range
power supply
cord
4-wire direct
A fused
disconnect or
circuit breaker
5"
box
(12.7 cm)
3-wire receptacle
A UL listed,
(NEMA type 10-50R)
250-volt
minimum,
40-amp, range
power supply
cord
3-wire direct
A fused
disconnect or
1"
(2.5 cm)
circuit breaker
box
3"
(7.6 cm)
4-wire connection: Power Supply Cord
Use this method for:
New branch-circuit installations (1996 NEC)
Mobile homes
Recreational vehicles
In an area where local codes prohibit grounding through the
neutral
1. Remove the ground-link screw from the range frame. Save
the ground link screw and cup washer. Bend the ground-link
away from the range so that it does not contact the range.
B
A
A. Ground-link screw
B. Cup washer
C. Ground-link bent away from range
Go to Section:
4-wire connection:
Power supply cord
4-wire connection:
Direct wire
3-wire connection:
Power supply cord
3-wire connection:
Direct wire
C