An audible „click" sound of each catch fastener will show you that it has completely snapped in.
Mount the nuts M8 at the top.
Attention:
The fitted mounting plate must be secured for transport – see Instructions for transport!
Changing the position of the mounting plate:
Loosen the nuts of the mounting and locking brackets until they barely sit on the thread of the T-head screw.
For disassembly turn the bracket by 90 degrees, insert it at the required place, turn it back 90 degrees.
Tighten the nut – the bracket will position itself.
Attention:
For torques – see Technical data!
The cabinets and the bases mounted underneath, if applicable, (accessories) are designed for screwing into the floor.
When using leveling feet (accessories), take measures to prevent tipping if necessary. In addition, depending on the width / depth and overall weight,
reinforcement brackets (accessories) must be installed between the leveling feet and the bottom of the cabinet / base, if necessary.
Existing openings or drill holes or those made at the site must be properly closed with devices or other fittings that are at least of the same IP protection
class as the cabinet.
Prior to putting the cabinet into service, the mechanical functions of the cabinet must be checked, in particular if the door closes properly. A visual
inspection of the seals which are relevant for the maintaining the protection class as well as of the protective conductor must be carried out.
The position of the key (standard: 3 mm double-mandrel) indicates if the door is securely locked.
Locked: 90° to the nearest outer edge of the door.
7. Instructions for Inspection, Maintenance and Repair
Please check at least once a year, in the framework of the inspection as determined by the operator, as appropriate:
lock and hinges for damage, stability and proper functioning,
door, top panel and cable gland plate seals for damage and whether they fit without gaps,
surface for damage (which might lead to loss of the IP protection class),
perfect condition of the attachment.
Adjust maintenance intervals to the ambient and operating conditions!
Clean the cabinet in regular intervals, in particular contaminated fittings, to avoid sluggishness and malfunctions. If necessary, fittings must be treated with
suitable lubricants.
Exchange damaged parts and use original häwa parts only. Minor flaws on painted surfaces such as scratches can be fixed using the häwa touch-up paint
for RAL 7035, order no. 3080-7035-03-75, alternatively 2K-PUR acrylic paint.
When purchasing spare parts please state the cabinet product code and your order number to ensure identification – see inside of door.

8. Technical Data

Open: Parallel to the nearest outer edge of the door.