7. Instructions for Inspection, Maintenance and Repair
Please check at least once a year, in the framework of the inspection as determined by the operator, as appropriate:
lock and hinges for damage, stability and proper functioning,
door and cable gland plate seals for damage and whether they fit without gaps,
surface finish for damages and that all drillings are closed (which might lead to loss of the IP protection class),
perfect condition of the (wall) attachment.
Adjust maintenance intervals to the ambient and operating conditions!
Clean the enclosure in regular intervals, in particular contaminated fittings, to avoid sluggishness and malfunctions. If necessary, fittings must be treated with
suitable lubricants.
Exchange damaged parts and use original häwa parts only. Minor flaws on painted surfaces such as scratches can be fixed using the häwa touch-up paint
for RAL 7035, order no. 3080-7035-03-75.
When purchasing spare parts please state the cabinet product code and your order number to ensure identification – see inside of door.

8. Technical Data

Static loads:
Maximum load, incl. weight of enclosure:
Maximum load on mounting plate:
Maximum load on doors 180° – see c):
Notes:
All specifications apply:
a) provided the load is evenly distributed on the surface or in the space.
b) for wall mounting using häwa wall-mounting brackets.
c) for installation and / or attachment on the floor (e.g. bases / feet) 50 N max. with 2 hinges or 100 N max. with 3 hinges.
IK protection class: IK08 (if used in compliance with its intended use and for cable gland plates at the bottom).
IP protection class: single door: IP66 / double door: IP55
Torque specifications:
The specifications stated below have been uniquely determined for standard sheet steel cabinets with standard finish and for stainless-steel cabinets
and are deemed to be binding under optimum conditions (e.g. straight fitting of thread-forming screws).
Wall mounting
Attachment of wall-mounting brackets (see Accessories) to body: 18 Nm
Cable gland plate (only sheet steel)
Attachment of cable gland plate(s) according to scope of delivery or variations thereof (see Accessories) to body: 1.5 Nm – after the thread is completely
formed.
Exception: cable gland plate with rubber filling 1 Nm – after the thread is completely formed.
Mounting plate even and folded
Mounting of mounting hardware to embossed rear panel (only sheet steel enclosures): 11 Nm
Attachment / locking of mounting plate:
Sheet steel: 11 Nm
Stainless steel: 10 Nm
Lock (after changing the opening direction of the door)
Attachment of lock casing to door panel (nut SW 27):
Sheet steel: 6 Nm
Stainless steel: 10 Nm
Attachment of latch to lock casing (screw M6): 6 Nm
Hinges (after changing the opening direction of the door)
Attachment of hinge bracket to body: 3,5 Nm
Protective conductor
Attachment of grounding cable / grounding straps to ground stud:
Sheet steel: 9 Nm
Stainless steel: 6 Nm
All technical details have been uniquely determined for products of the 33 series.
up to W x H in mm: 600 x 800
more than this:
unfolded
folded
2 hinges
3 hinges
2,500 N
4,000 N
2,000 N
3,000 N
400 N