Concrete Slab Installations – Exhaust Through Wall
A
B
C
O
N
M
A. Wall cap
B. 6" (15.2 cm) round metal vent
C. 16" (40.6 cm) maximum
D. 6" (15.2 cm) round PVC sewer pipe
E. 3
/
" x 10" (8.3 cm x 25.4 cm) rectangular 90° metal vent elbow
1
4
F. 3
/
" x 10" (8.3 cm x 25.4 cm) rectangular to 6" (15.2 cm)
1
4
round metal vent transition
G. 6" (15.2 cm) round PVC coupling
H. Concrete slab
I. 6" (15.2 cm) round PVC sewer pipe
J. 6" (15.2 cm) round 90° PVC sewer pipe elbow
K. Tightly pack gravel or sand completely around pipe.
L. 30 ft (9.1 m) maximum
M. 6" (15.2 cm) round 90° PVC sewer pipe elbow
N. 6" (15.2 cm) round PVC coupling
O. 12" (30.5 cm) minimum
Calculating Vent System Length
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
Vent Piece
6" (15.2 cm) Round
45° elbow
2.5 ft (0.8 m)
90° elbow
5.0 ft (1.5 m)
6" (15.2 cm) wall cap
0.0 ft (0.0 m)
3Z\v" x 10"
4.5 ft (1.4 m)
(8.3 cm x 25.4 cm)
to 6" (15.2 cm)
transition
6" (15.2 cm)
1 ft (0.3 m)
to 3Z\v" x 10"
(8.3 cm x 25.4 cm)
transition
3Z\v" x 10"
5.0 ft (1.5 m)
(8.3 cm x 25.4 cm)
to 6" (15.2 cm)
90° elbow transition
8
E
F
D
G
H
I
L
J
K
Vent Piece
6" (15.2 cm) Round
6" (15.2 cm)
5.0 ft (1.5 m)
to 3Z\v" x 10"
(8.3 cm x 25.4 cm)
90° elbow transition
3Z\v" x 10"
5.0 ft (1.5 m)
(8.3 cm x 25.4 cm)
90° elbow
3Z\v" x 10"
5.0 ft (1.5 m)
(8.3 cm x 25.4 cm)
flat elbow
3Z\v" x 10"
0.0 ft (0.0 m)
(8.3 cm x 25.4 cm)
wall cap
Example vent system
90˚ elbow
2 ft
(0.6 m)
1 - 90° elbow
8 ft (2.4 m) straight
1 - wall cap
System length
NOTE: A flexible vent is not recommended. Flexible vents
create back pressure and air turbulence that greatly reduce
performance.
Recirculation: Non-Vented (Recirculating)
Installations Only
You will need to order:
Recirculation Kit part number W10807915 (See the
■
"Assistance or Service" section in your Use and Care
manual to order.)
You may also need a section of 3Z\v" x 10" (8.3 cm x 25.4 cm)
■
metal duct – length required is determined by the distance
from the exhaust outlet to the back flat surface of the
Recirculation Kit housing.
wall cap
6 ft (1.8 m)
= 5 ft (1.5 m)
= 8 ft (2.4 m)
= 0 ft (0 m)
= 13 ft (3.9 m)