Electrical Connection; Technical Data - IFM Electronic AS-interface AC2264 Notice De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Electrical connection

Disconnect the supply circuits for the actuators from power!
Connect the sensors and actuators with the terminals. Do not
connect the inputs I1 to I4 and I+, I- with an external potential.
Connection
A+:
AS-i +
A-:
AS-i -
I+:
sensor supply +24 V
I-:
sensor supply
E+:
actuator supply +24 V
E-:
actuator supply 0 V
I1 ... I4:
switching inputs sensors 1...4
O1 ... O3: switching outputs actuators 1...3
O-:
Switching output actuator 0 V
LEDs 1:
switching status indication
sensor inputs
LEDs 2:
AS-i, FAULT, AUX
LEDs 3:
switching status indication
actuator outputs
ADR:
addressing socket
Operation
Check the safe functioning of the unit. Display by LEDs:
• LED green: voltage supply via the AS-i network O.K.
• LED yellow: input / output switched
• LED red: AS-i communication error, e. g. slave address 0
• LED red flashing: periphery fault, e.g. no sensor supply / overload or
short circuit of the output

Technical data

You can download the data sheet from the Internet if required
(www.ifm.com).