4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault, the 3 LEDS will indicate the fault code.
There are faults that cause permanent shutdown: to restore operation, press the RESET button for 1 second (ref. 5 - fig. 1) or RESET on the optional remote timer control if installed;
if the boiler fails to start, it is necessary to firstly eliminate the fault indicated in the operation LEDs.
Other faults cause temporary shutdowns which are automatically reset as soon as the value returns within the boiler's normal working range.
Table. 3 - List of faults (Legend - LEDs
Fault
No burner ignition
Overtemperature protection activation
Flame present signal with burner off
Fume thermostat activation (boiler operation is prevented for 20
minutes after fume thermostat intervention)
Low system pressure
Delivery sensor fault
DHW sensor fault
Exchanger protection activation.
(The LEDs flash alternately)
Faulty card
Card not electrically powered

5. TECHNICAL DATA AND CHARACTERISTICS

Table. 4 - Legend - figures of cap. 5
7 Gas inlet
8 Domestic hot water outlet
9 Cold water inlet
10 System delivery
11 System return
14 Safety valve
19 Combustion chamber
22 Burner
27 Copper exchanger for heating and hot water
32 Heating circulating pump
34 Heating temperature sensor
36 Automatic air vent
37 Cold water inlet filter
38 Flow switch
= Off /
= On /
= Fast flash.)
Green
Yellow
Red
39 Water flow limiter
42 DHW temperature sensor
44 Gas valve
49 Safety thermostat
56 Expansion tank
74 System filling cock
78 Anti-backflow device
81 Ignition and detection electrode
95 Diverter valve
114 Water pressure switch
126 Fume thermostat
194 DHW exchanger
241 Automatic bypass
cod. 3541F171 - Rev. 02 - 02/2018
Possible cause
No gas
Ignition/detection electrode fault
Faulty gas valve
Ignition power too low
Heating sensor damaged
No water circulation in the system
Air in the system
Electrode fault
Card fault
Fume thermostat contact open
Wiring disconnected
Flue not correctly sized or obstructed
System empty
Water pressure switch damaged or not connected
Sensor damaged
Wiring shorted
Wiring disconnected
Sensor damaged
Wiring shorted
Wiring disconnected
No system H
O circulation
2
Air in the system
Card failure
No power
Blown fuses
Cure
Check the regular gas flow to the boiler and that the air has been elimi-
nated from the pipes
Check the wiring of the electrode and that it is correctly positioned and
free of any deposits
Check the gas valve and replace it if necessary
Adjust the ignition power
Check the correct positioning and operation of the heating sensor
Check the circulating pump
Vent the system
Check the ionisation electrode wiring
Check the card
Check the thermostat
Check the wiring
Change the flue
Fill the system
Check the sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the circulating pump
Vent the system
Replace the card
Check the power supply
Replace fuses
EN