Steca Grid 8000 3ph Instructions D'installation Et De Service page 50

Masquer les pouces Voir aussi pour Grid 8000 3ph:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Parameter
Safety
Protection degree
Isolation principle
Grid monitoring
Isolation monitoring
Residual current monitoring
Application conditions
Area of application
Corrosion categories
Ambient temperature
Relative humidity
Noise emission
Equipment and design
Degree of protection
DC connection
AC connection
Dimensions (X x Y x Z)
Weight
Communication interface
Integrated DC circuit breaker
Cooling principle
Test certificate
50
StecaGrid 8000 3ph
no galvanic isolation, transformerless
MSD, compliant with DIN VDE 0126-1-1
Yes, integrated; in addition, the plant must be equipped with an AC/DC sensitive re-
sidual current protection switch type B in accordance with DIN VDE 0100-410.
indoor rooms with or without air conditioning, outdoors with protection
C3 (urban and industrial atmosphere, coastal areas with low salt concentration)
MultiContact MC4 (3 pairs), rated current
of 22 A per input
Wieland RST25i5 plug for cable cross-sections ≤ 4 mm
RS485 plug-in card (included in delivery), 2 x RJ45 sockets, can be connected to
Meteocontrol WEB'log or Solar-Log
yes, compliant with VDE 0100-712
temperature-controlled fan (variable speed)
CE mark, G83
projected: clearance certificate, DK5940
737.096 | 11.37
EN
Value
StecaGrid 10000 3ph
I
yes, integrated
–20 °C ... +60 °C
0% ... 95%
< 60 dBA
IP54
MultiContact MC4 (5 pairs), rated current
of 22 A per input
2
, counterpart socket provided
400 x 847 x 225 mm
42 kg
StecaGrid Vision,
clearance certificate, CE mark, G83,
DK5940, AS4777