Gas Supply Connection; Make Gas Connection - Maytag MDE20PDAGW Instructions D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

If an Exhaust Hood Cannot be Used
The outside end of main vent should have a sweep elbow
directed downward.
* Minimum clearance above
any accumulation of snow,
ice, or debris such as leaves
If main vent travels vertically through the roof, rather than
through wall, install a 180° sweep elbow on end of vent at least
610 mm (2 ft.) above surface of roof.
The opening in wall or roof shall have a diameter 13 mm (1⁄2")
larger than vent diameter. Vent should be centered in opening.
Do not install screening over end of vent for best performance.

Make Gas Connection

1. Connect gas supply to dryer. If the flexible gas hose has
10 mm (3/8") BSP thread, use the supplied conversion
thread adapter. Use pipe-joint compound resistant to the
action of L.P. gas for gas connections.
DRYER VENTING REQUIREMENTS
Multiple Dryer Venting
A main vent can be used for venting a group of dryers. The
main vent should be sized to remove 5663 l/min. (200 CFM) of
air per dryer. Large-capacity lint screens of proper design may
be used in main vent if checked and cleaned frequently. The
room where the dryers are located should have make-up air
equal to or greater than CFM of all the dryers in the room.
Back-draft dampers are available from your distributor and
should be installed in the vent of each dryer to keep exhausted
air from returning into dryers and to keep exhaust in balance
within main vent. Unobstructed return air openings are required.
Although usually each single-load dryer should have an
unobstructed outdoor air opening of 154 cm
on 6.5 cm
air openings are also acceptable. Set up common openings so
the make-up air is distributed equally to all of the dryers. Keep
in mind that the coverage area must be increased by 33% to
account for the use of registers or louvers over the openings.
Also, make-up air openings should not be installed near the
location where exhaust vents exit the building.
Each vent should enter the main vent at an angle pointing in
the direction of the airflow. Vents entering from the opposite
side should be staggered to reduce the exhausted air from
interfering with the other vents.
The maximum angle of each vent entering the main vent should
be no more than 30°.
Keep air openings free of dry cleaning fluid fumes. Fumes
create acids which, when drawn through the dryer heating
units, can damage dryers and items being dried.
A clean-out cover should be located on the main vent for
periodic cleaning of the vent system.
NOTE: For more dryer venting information, please refer to
Whirlpool document W10100920.

GAS SUPPLY CONNECTION

If necessary for service, open the toe panel. Use a putty
knife to press on the 2 toe panel locks located at the top
of the toe panel. Pull downward on the toe panel to open.
Toe panel is hinged at the bottom.
2. Open the shut-off valve in the gas supply line and make
sure the dryer has its own gas supply opened.
3. Test all connections by brushing on an approved
noncorrosive leak-detection solution. Bubbles will show
a leak. Correct any leaks found.
[1 in.
] per 252 kcal [1,000 Btu]), common make-up
2
2
Air Flow
Air ow
(on some models)
(24 in.
) (based
2
2
30˚ max.
17

Publicité

Table des Matières
loading

Table des Matières