3.4 ELECTRICAL WIRING

~
50Hz 230V
PE L
Safety
thermostat
7 pin plug
7 pole socket
D4022
Ignition
electrodes
Fig. 9
B
A
2325
N
Main switch
T6A
Limit
thermostat
Black
Blue
Brown
Black
White
Blue
Heater with start
Burner-earth
Green led (Fan)
Yellow led (Heater)
Red led
(Lock-out signalling due to failure to shut-down)

CONTROL BOX

To remove the control-box from the burner, loosen screw (A, fig. 9)
and pull to the arrow direction, after removing all components, the
7 pin plug and earth wire.
In case of disassembly of the control box, retighten the screw
(A) with a torque wrench setting of 1 – 1.2 Nm.
For burners installed on air generators, remove the bridge (B, fig. 9)
E9070
from the control box.
WARNING
DO NOT EXCHANGE NEUTRAL WITH PHASE
NOTES:
– Wires of min. 1 mm
otherwise by local standards and legislation).
– The electrical wiring carried out by the installer
must be in compliance with the rules in force in
the Country.
Hour counter
(230V - 0.1A max.)
Remote lock-out signal
(230V - 0.5A max.)
Photoresistance
Oil valve
Motor
thermostat
5
GB
2
section. (Unless requested
(See page 4)
Connect the automatic shut-off
device (230V - 0.5A max.) to
the clamps N - T2 of the 7 pin
plug.
TESTING
Check the shut-down of the
burner by opening the thermo-
stats and the lock-out by dark-
ening the photoresistance.
Capacitor