3.1 Connection overview

A
E
C
A
Mains power socket
B
Auxiliary output terminals
(outputs 3 to 5)
C
Temperature sensor socket
D
Main output terminals
(outputs 1 to 2)
E
Alarm reports
F
Battery terminal
Important: the openings provided in the cabinet must be kept free. Do not create additional
openings because this can cause the device to malfunction and voids the warranty.

3.2 Connection specifications

-
Mains: 2.5 mm².
Battery: 16 mm².
-
'Amplifiers' load (outputs 1 and 2): 16 mm².
-
'Controlers' load (outputs 3 to 5): 2.5 mm².
-
-
Alarm reports (plug-in): 1.5 mm².

3 Connection

B
F
D
Figure 4 : Rear side view of equipment
Socket for connecting the battery charger to the mains
Three auxiliary output terminals (5 A max.). The outputs are
protected by a fuse (Faux1 to Faux3).
Socket to connect the temperature sensor.
Two output terminals (40 A max.). The outputs are
protected by a fuse (F1 to F2).
Fail-safe, dry contact, three-pole SPDT switch (C- NC-
NO), allowing 1 A at 24 Vdc or 0,5 A at 120 Vac:
A
B
C
Terminal for connecting the battery leads (40 A max.).
Mains status
Battery status
Output voltage status