4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler anomaly, the 3 LEDS will indicate the fault code.
There are faults that cause shutdown: in order to restore operation it suffices to press RESET for 1 second (ref. 5 - fig. 1) or perform a RESET on the optional remote timer control if
this is installed. If the boiler fails to start, you must first resolve the fault indicated on the display.
Other faults cause temporary shutdowns which are automatically reset as soon as the value returns within the boiler's normal working range.
Table. 9 - List of faults (Legend Leds
Fault
No burner ignition
Flame present signal with burner off
Air pressure switch (fails to close contacts
within 20 sec. of fan activation)
Low system pressure
Delivery sensor fault
DHW sensor fault
Exchanger protection activation.
(The LEDs flash alternately)
Faulty card
Card not electrically powered

5. TECHNICAL DATA AND CHARACTERISTICS

Table. 10 - Legend - figures of cap. 5
5 Sealed chamber
7 Gas inlet
8 Domestic hot water outlet
9 Cold water inlet
10 System delivery
11 System return
14 Safety valve
16 Fan
19 Combustion chamber
22 Burner
27 Copper exchanger for heating and hot water
28 Fume manifold
29 Fume outlet manifold
32 Heating circulating pump
34 Heating temperature sensor
36 Automatic air vent
= Off /
= On /
= Fast flash)
Green
Yellow
Red
37 Cold water inlet filter
38 Flow switch
39 Water flow limiter
42 DHW temperature sensor
43 Air pressure switch
44 Gas valve
49 Safety thermostat
56 Expansion tank
74 System filling cock
81 Ignition and detection electrode
95 Diverter valve
114 Water pressure switch
187 Fume baffle
194 DHW exchanger
241 Automatic bypass
364 Condensate union
cod. 3541F161 - Rev. 00 - 05/2014
Possible cause
No gas
Ignition/detection electrode fault
Faulty gas valve
Ignition power too low
Electrode fault
Card fault
Air pressure switch contact open
Faulty air pressure switch wiring
Faulty baffle
Flue not correctly sized or obstructed
System empty
Water pressure switch damaged or not connected
Sensor damaged
Wiring shorted
Wiring disconnected
Sensor damaged
Wiring shorted
Wiring disconnected
No system H
O circulation
2
Air in system
Card failure
No power
Blown fuses
Cure
Check the gas flow to the boiler and that the air has been eliminated from the pipes
Check the wiring of the electrode and that it is correctly positioned and free of any
deposits
Check the gas valve and replace it if necessary
Adjust the ignition power
Check the ionisation electrode wiring
Check the card
Check the wiring
Check the fan
Check the pressure switch
Replace the baffle
Fill the system
Check the sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the circulating pump
Vent the system
Replace the card
Check the power supply
Replace fuses