13
Use a back-off wrench when fastening the hydronic connections !
14
When the condensate drain pipes are being connected, the pipe
system must be sufficiently supported in order to prevent strain on
the condensate drain tray.
16
PE
L
N
Connect the device electrically.
JAGA N.V. | CLIMA CANAL PLUG & PLAY | MANUEL | 2021.05.03 | V.01
15
0 2cm
The condensate drain system must be set up with an adequate
p-trap in order to prevent the infiltration of odours. Always install
a plug for cleaning in the lower part of the p-trap in order to allow
quick disassembly.Pour water into the condensate collection pan
and check if the liquid is drained properly. Otherwise, check the
inclination and look for possible blockages.
EN
3 cm/m