TECHNICAL DATA

Compact wall-mounted units – KWL EC 360 W/W ET
We recommend that you consult the responsible chimney sweep in order to accommodate your wishes before purcha-
sing an underpressure monitoring system for fireplaces.

3 .0 Unit overview

3
15
11
15
8
Pos .
Name
1
Exhaust air fan
2
Supply air fan
3
Intake air filter cover
4
Panel
5
Unit door
Back panel
6
7
Silencer
8
Heat exchanger
9
Design panel
3 .1
Technical data
KWL EC 360 W/W ET
Voltage/frequency
Rated current – ventilation
Rated current – preheater
Rated current – max. total
Electrical preheater (output)
Summer bypass
Electrical supply line to subdistribution board
Flow rates V m
3
/h (9 levels)
Temperature operating range
Temperature installation area
Protection category
Weight
Heat exchanger
4
5
9
9
7
12
16
17
1~ 230 V~/50 Hz
0 .5 A
6 .3 A
0 .5 A (6,8 A incl. preheater)
1 .0 kW (accessories)
automatic (adjustable)
NYM-J 3 x 1 .5 mm
410/ . . . /not specified
-20 °C to +45 °C
+5 °C to +45 °C (< 90 % relative humidity, non-condensing)
IP30
72 kg (KWL EC 360 W) / 70 kg (KWL EC 360 W ET)
Plastic
4
13
1
2
10
Pos .
Name
10
Siphon
11
Extract air filter cover
12
Terminal box
13
RJ adapter board
14
Wall bracket
Filter Coarse 65 % extract air
15
Filter Coarse 65 % supply air
16
Filter ePM1 50 % supply air
Bypass motor
17
2
Fig .1