Technical Specifications - Daikin EPIMSA6 Manuel D'installation

Masquer les pouces Voir aussi pour EPIMSA6:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

EPIMSA6
EPIB6
The Master/Slave interface or Power interface must
be installed to use microprocessor-based control panels
on the whole range of units for models with a current
consumption greater than 5 A.
The EPIMSA6 Master/Slave interface is used for
connecting up to 4 units in parallel to 1 controller
FWEC(1,2,3)A. Up to 3 EPIMSA6 interfaces can be
connected in parallel to 1 controller. The capacity of the
EPIMSA6 contacts is 4 x 3 A.
The EPIB6 Power interface permits to use the electronic
remote controller FWEC(1,2,3)A on the whole range of
units with a current consumption greater than 5 A. The
capacity of the EPIB6 contacts is 16 A.
Neglecting the absolute requirement to install
an additional interface (EPIB6 or EPIMSA6) to
units with a current consumption greater than
5 A may cause fire or other damage to the
equipment.
Table below lists the maximum current of the whole
range of units.
FWL/FWM/FWV
01
0.16 A
02
0.21 A
03
0.27 A
04
0.39 A
05
-
06
0.38 A
07
-
08
0.80 A
09
-
10
1.12 A
12
-
16
-
18
-
<=3 A
Master/Slave function is possible by installing the EPIMSA6.
>3 A
Installing EPIMSA6 you must install EPIB6.
>5 A
EPIB6 must be installed.
Installation manual
1
Master/Slave interface
Power interface
FWB
FWD
-
-
0.56 A
-
0.56 A
-
0.56 A
0.95 A
1.10 A
-
1.10 A
1.58 A
1.10 A
-
1.40 A
1.97 A
1.40 A
-
1.40 A
1.97 A
-
3.21 A
-
5.37 A
-
5.37 A
T
S
EchNical
Power supply
Contacts at output
Operating temperature
Humidity limits (RH)
Protection rating
Container
Weight
i
NSTallaTiON
n All field wiring and components must be
installed by a licensed electrician and must
comply with relevant local and national
regulations.
n Before obtaining access to terminals, all
power supply circuits must be interrupted.
n The EPIMSA6 or EPIB6 interfaces are to be installed
on a DIN guide, usually housed in the electric boards
cabinet.
n The overall dimensions of the EPIMSA6 and EPIB6
interface are shown in figure 3.
n Make the electrical connections with POWER OFF as
indicated in the diagrams of figure 1+2 that show the
following:
Figure 1: microprocessor-based controller + 2x
EPIMSA6 connected to 8 units.
Figure 2: connections of EPIB6
Each unit requires a switch (IL) on the power supply line
with a distance of at least 3 mm between the opening
contacts, and a suitable safety fuse (F).
NOTE
Connect only one unit per EPIMSA6 or
EPIB6 output.
4PW17562-1A
Installation manual
pEcificaTiONS
EPIMSA6
230 V
–15% +10% 50 Hz
4x3A 250 V
0~40°C
20~80% non-condensing
IP30
105 x 90 x 70 mm
265 g
Master/Slave interface + Power interface
EPIB6
1x16A 250 V
EPIMSA6 + EPIB6

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Epib6

Table des Matières