WARNING
Read all safety warnings, instructions, illustrations
and specifications provided with this product.
Failure to follow all instructions listed below may
result in electric shock, fire and/or serious injury.
Save all warnings and instructions for future
reference.
Features
- Microprocessor-controlled synchronous
electronics BSY+ for safe and precise
synchronous running of up to 4 drives
- Individually programmable via software SCS*
- SHEV-high speed function (fast-running feature in
OPEN-direction)
- Closing edge protection for the main closing edge
- Especially quiet motor running in ventilation mode
- Optinal with "-AS2" = protection class 2 and
"-AS3" as well as "-LS" = protection class 3
* only with BI-BT2
(electronically isolated due to Bluetooth)
Safety notes
Operating voltage 230 V AC!
Risk of injury from electric shock!
Do not reverse L+N! Connect PE!
The BSY+ bus also operates with 230V!
- Connection must be carried out by a certified
electrical technician
- Danger of crushing hands and fingers!
- Keep people away from the operating area of
the drive
- Keep children away from the control
- Observe pressure load diagram of the gear
rack!
- Use only in dry rooms
- Suitable for indoor mounting only. Use rain
detector in the event that there is a risk of rain
- Use option "-W" if mounted outdoors!
- Use unmodified original D+H parts only
- Observe the bracket-set mounting instructions
Observe enclosed red safety note!
Scope of supply
Drive unit with 2.5 m silicone cable. Depending on
the type of window, different bracket sets are
available separately.
6/20
DXD 150/300 -K-BSY+ (-HS)
Intended use
- Rack and pinion drive for electric opening and
closing of heavy windows and flaps in the facade
and roof area
- Operating voltage 230 V AC
- Up to 4 drives possible
- Useable for smoke extraction, D+H Euro-SHEV in
accordance with DIN EN 12101-2 as well as daily
ventilation
- Suitable for indoor mounting only
Pressure load diagram
Maximum pressure load of the toothed rack is not
automatically identical with the maximum pressure
force of the drive!
With Type DXD 150-K-BSY+ (-HS) are loads of over
1000 N to 1500 N are only briefly permissible (e.g. for
throwing off snow or with wind loads). These may
arise up to a stroke of 1750 mm.
With Type DXD 300-K-BSY+ (-HS) are loads of over
2000 N to 3000 N are only briefly permissible (e.g. for
throwing off snow or with wind loads). These may
arise up to a stroke of 1500 mm.
3500
3000
2500
2000
1500
1000
500
0
3500
3000
2500
2000
1500
1000
500
0
English
DXD 150-K-BSY+ (-HS)
durable
temporary
Stroke (mm)
DXD 300-K-BSY+ (-HS)
durable
temporary
Stroke (mm)
99.824.28 1.5/02/16