Material
Lid fixing
Mounting
Temperature sensor
Type
sensor cable
Diameter sensor cable
Diameter sensor head
Max. exposure temperature
sensor cable
Sensor characteristic
Temperature (°C)
– 0
+ 25
+ 50
+ 70
+ 100
TC RU C-BE.БЛ08.B.01634
The sensor cable can be extended up to 100 m when a cross section of 1.5 mm
cable will be extended no live cables should be laid in parallel to avoid inductive interferences.
Installation of heating cable
Follow the „General installation instructions for self-regulating heating cables". Max. circuit lengths
are WinterGard FS-A-2X: 150m, FS-B-2X: 105m, FS-C-2X: 90m, FroStop Green: 100m, FroStop
Black: 80m. Use a contactor for longer heating circuit lengths.
Functional description
When the temperature exceeds the adjusted setpoint value, the switching contact opens and
switches the heating cable off.
When the temperature falls below the setpoint value, the switching contact closes. The
integrated green LED display lights up to indicate that the heating cable is switched on. In
the event of sensor break or shortcircuit, the switching contact closes. In the event of loss
a power supply, the switching contact opens. The integrated red LED display lights up to
indicate that there is a defect.
ABS
Zn AL 4 Cu1 nickel plated quick release screws in four places
RAYCHEM support bracket JB-SB-01 or wall mounting
PTC KTY 83-110
3 m
± 5,5 mm
6,5 mm
160°C
Resistance (Ohm)
820
1000
1202
1379
1670
is used. If sensor
2
nVent.com | 3