Section 1: Introduction; What's New To Version 5.X; How To Use This Manual; Specifications And Features - DSC PowerSeries RF5132-433 Manuel D'installation

Masquer les pouces Voir aussi pour PowerSeries RF5132-433:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

This manual describes how to install, program and maintain the RF5132-433.
Before you install the RF5132-433 module, you should complete the following steps in your system installation:
1. Plan the installation and wiring of the security system (see your system Installation Manual).
2. Install the control panel, and install and enroll at least one keypad to use for programming.
3. Install and enroll any hardwired zone expander modules (PC5108) you plan to use.
Program the RF5132-433 from a system keypad or using downloading software on a remote computer. Read your
system Installation Manual for more information.

1.1 What's New to Version 5.X

1. Section 2.3 Connect the RF5132-433 Receiver - a fifth terminal was added to the RF5132-433 which should
remain unused.
2. Section 2.4 Tamper - programmable wall and case tamper for RF5132-433.
3. Section 3.5 LED - addition of LEDs to assist in installation.
4. Section 6.1 Trouble Conditions - addition of RF delinquency (EU only).
5. Programming Sections [61] - [69] - 8 partition support for wireless devices.
6. RF5132-433 v5.0 DLS Driver Pack is required for this product.

1.2 How to Use this Manual

Read this manual before you begin installing the RF5132-433. To install and set up the RF5132-433 and wireless
devices, follow these steps. Refer to the sections listed below.
1. Temporarily mount and wire the RF5132-433 module (see Section 2).
2. Enroll and program wireless devices (see Section 3).
3. Complete zone and other programming on the system (see Section 4).
4. Test the placement of all the wireless devices (see Section 5).
5. Permanently mount the RF5132-433 receiver and wireless devices (see Section 5).
For additional information on trouble conditions, RF jamming signal detection and battery replacement, see Section 6.
For help with troubleshooting, see Section 7.

1.3 Specifications and Features

• Current Draw: 50 mA
• Frequency: 433 MHz
• Zones - receiver can receive signals from up to 32 wireless zones and 16 wireless keys
• Supervisory - programmable supervisory window
• Location
- can be wired up to 750 ft. / 230 m from the main panel with 22 gauge wire
- connects to Keybus
- for longer wire runs, thicker gauge wire must be used.
• Compatibility: The RF5132-433 v5.X can be connected to the following panels: PC501X, PC5020, PC1555, PC580,
PC1616, PC1832, PC1864.
• Operating temperature: 0-50°C / 32-122°F
• Separate built-in wall and case tamper

Section 1: Introduction

3

Publicité

Table des Matières
loading

Table des Matières