Electrical
Wiring (Figure 9)
1. Install, ground, wire and maintain pump in accor-
dance with your local electrical code and all other
codes/ordinances that apply. Consult your local
building inspector for local code information.
2. Ground pump permanently using wire of size and
type specified by approved local or national codes.
Risk of explosion. Do not ground to gas
supply line.
3. Connect ground wire first. Connect to ground first,
then to green grounding terminal provided on pres-
WIRING CHART – Recommended Wire and Fuse Sizes
MOTOR
VOLTS
HP
1
115/230
(*)Time delay fuse or circuit breakers are recommended in any motor circuit.
For parts or assistance, call Flotec Customer Service at
MAX.
BRANCH FUSE
LOAD
RATING
AMPS
AMPS*
19.2/9.6
20/15
sure switch identified as GRD. Ground connection
MUST be made to this terminal. Do not connect
motor to electrical power supply until unit is perma-
nently grounded; otherwise serious or fatal electrical
shock hazard may be caused.
4. For best ground connection, connect to grounded
lead in service panel or to metal underground water
pipe or well casing at least 10 ft. (3 M) long. If plastic
pipe or insulated fittings are used, run ground wire
directly to metal well casing or use ground electrode
furnished by the power company.
DISTANCE IN FEET (M) FROM MOTOR TO SUPPLY
0 - 100
101 - 200
(0 - 30)
(30 - 61)
10/14 (5/2mm
2
)
8/12(7/3mm
1-800-365-6832
10
201 - 300
(61 - 91)
2
)
6/12(13/3mm
2
)