Connection Diagram; Cable Entry (Kle); Blanking Plug; Closing The Device - Cooper Crouse-Hinds GHG 525 45 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Code for voltage and No. of poles
acc. to IEC
Voltage
2-pole + PE
110 - 130V 50/60Hz
200 - 250V 50/60Hz
3-pole + PE
200 - 250V 50/60Hz
480 - 500V 50/60Hz
380 - 415V 50/60Hz
600 - 690V 50/60Hz
3-pole + N + PE
480 - 500V 50/60Hz
380 - 415V 50/60Hz
600 - 690V 50/60Hz
Contact arrangement with switch
3-pole+PE
3-pole + N + PE
Standard
Fig. 9
Item 1
6.3
Cable entries (KLE);
blanking plugs
6.3.1
Plug and socket
Flexible cables shall be used with trumpet-
shaped cable glands or other suitable
entries with additional pull-relief.
10
10
10
10
10
Cooper Crouse-Hinds GmbH
Plug and socket system 125A, GHG 525
When using cable entries with a lower IP
protection than that which applies to the
device (see page 7, technical data), the IP
protection of the whole device will be reduced.
The mounting directives applicable to the
cable entries used shall be observed.
Unused holes shall be closed with a blanking
plug in order to establish the minimum
protection category.
In case of sealing inserts that are cut out, it
shall be ensured that the insert is properly
adapted to the cable diameter.
Care has to be taken that when fitting the
Clock
cable entries, sealing inserts appropriate to
face
the cable diameter are used.
Colour (PE)
In order to ensure the required minimum
yellow
4 h
protection category, the cable glands are to
blue
6 h
be tightened down.
blue
9 h
Overtightening might impair the protection
black
7 h
category.
red
6 h
black
5 h
Attention: Metal flanges, metal plates and
metal cable glands shall be included in the
black
7 h
equipotential earth connection.
red
6 h
black
5 h
6.3.2
Plug and coupler
Fig. 9:
In general, only the sealing inserts fitted in the
plug and coupler may be used.
When mounting the cable, attention has to be
paid that sealing inserts matching the cable
diameter be used.
After having connected the cable, the
Optional
coupling ring item 2 is to be screwed
fingertight until the sealing effect is obtained.
Then the screws item 4 of the pull-relief, item
Item 3 Item 4
3, are to be tightened down.
Mind! Overtightening might impair the pull-
relief effect!
6.4

Closing the device

Item 2
In order to ensure the required minimum
protection category, the cover screws, the
screws of the plug and of the coupler shall be
tightened down.
Overtightening might impair the protection
category.
Any foreign matter shall be removed from
the device.
6.5

Taking into operation

Prior to taking the apparatus into operation,
the tests specified in the relevant national
regulations shall be carried out. Apart from
that, the correct functioning and installation of
the apparatus in accordance with these
operating instructions and other applicable
regulations will have to be checked.
Check the plug for any damages before
putting it in the socket.
The user must ensure that a uniform
equipotential earth applies throughout when
the plug and socket system is operated.
The inappropriate installation and
operation of the plugs and sockets can
entail the loss of warranty.
7

Maintenance/Servicing

Before opening the enclosure, make sure
that the device is disconnected from the
voltage, or take appropriate protective
measures.
The required maintenance intervals depend on
the specific application and will therefore have
to be determined by the user dependent on
the conditions of use.
If during servicing, repairs prove to be
necessary, section 8 of these operating
instructions will have to be observed.
8
Repair/Overhaul/
Modifications
Repairs and overhaul may only be carried out
with genuine CEAG spare parts.
Modifications to the device or changes of
its design are not permitted.
9

Disposal/Recycling

When the apparatus is disposed of, the
respective national regulations on waste
disposal will have to be observed. In order to
facilitate the recycling of individual
components, plastic parts are provided with
the identification mark of the plastic material
used.
Subject to modifications or supplement of the
product range

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ghg 525 75Ceag ghg 525 45Ceag ghg 525 75

Table des Matières