TX Series Owners Manual
4) Remove auxiliary materials package and documentation.
Positioning
Outdoors or indoors.
Level.
Access to drain.
Access to electrical hookup.
Access to adequate water supply.
After moving the unit to the installation site, select an
area where the unit can be serviced from the top and
front. When installing next to a wall, leave a minimum of
a 6" access to the back of the unit. Leave a minimum of
6" on both sides of the system. 36" access in front of the
system is required for the electrical control box.
Plumbing Hook-ups
1) Connect the feed water line to the inlet of the TX 1440 Whole House RO (1). The connection on the RO is
1/2" FNPT, and is directly on the inlet solenoid valve.
2) From the check valve, connect your permeate line using 3/8" tubing (2). This connection should lead to
an atmospheric holding tank or to a pneumatic air charge tank.
3) Connect the drain line using 1/2" tubing (3). This connection should be made to a drain in compliance
with the local codes and requirements in your area.
4) In addition to the RO plumbing hook-up, it is recommended to install a system by-pass using adequately-
sized ball valves.
PSI Switch
Arrow on
Check Valve
Denotes
Flow Direction
Permeate (2)
Drain (3)
Kinetico Incorporated Corporate Headquarters Newbury, Ohio 44065 440-564-9111
Rev. 11/2016
A
DETAIL
Inlet (1)
Figure 2
13
6"
6"
6"
36"
System Clearances
Figure 1
A
Product No. 13591E