6.4 AC input switch
Maximum AC switch power
(protected by 16 A Thermal Circuit Breaker)
Switch-over time inverter to AC input
Switch-over time AC input to inverter (U batt >10,5 V)
Detection time AC input fault
Trip level mains to inverter
Trip level inverter to mains
Min. - Max. frequency range (50 Hz / 60 Hz)
1
Inverter runs parallel with the AC input
6.5 Mechanical
12/800
/ 35
12/800
Cabinet
aluminum, protecting class IP21
color
Blue RAL 5012
Dimensions
375 mm x 215 mm x 115mm (See Anhang A)
(H x W x D)
weight (kg)
9
10
Battery-
1.5 m
1.5 m
connection
cable
AC in/out
Connection
2 * G-ST18i connector
Start battery
Terminals on printed board
connection:
(connector suitable for 1 mm
External
Remote switch (connector for 3 wire Ø 1mm
connection:
sensing,
Battery temperature sensor (connector for 2 wire Ø 1mm
remote switch
Alarm: transistor, open collector 66 40mA
(connector for 2 wire Ø 0,5 mm
Serial interface
For Phoenix Remote Control
(UTP
For Mk.1 with VEConfigure software
connector)
26
.
12/1200
12/1600
24/800
/ 50
/ 70
/ 16
12/1200 12/1600
24/800
10
9
1.5 m
1.5 m 1.5 m
2,5 mm²
2
wires)
2
)
3600 W
1
0 ms
1
0 ms
4 ms to 20 ms
180 VAC
187 VAC
45 – 55 Hz or 55 – 65 Hz
24/1200
24/1600
48/1200
/ 25
/ 40
24/1200 24/1600
48/1200
10
10
10
1.5 m
1.5 m
2
)
2
)
48/1600
/ 12
/ 20
48/1600
10
1.5 m