Pac Alpha
Test pressure
Operating pressure
Head Loss
Minimum water flow‐rate
Average water flow‐rate
Maximum water flow‐rate*
* this flow‐rate must not be exceeded
Elimination of condensation:
Warning: your device can produce several liters of water per day. You are strongly recommended to guide
the flow to drains.
2.4 Electrical connections
2.4.1 Voltage and protection
the electrical supply to the heat pump must pass via a protection and disconnection device (not supplied)
complying with the standards and regulations in force in the country,
the device is designed for connection to a general power grid with TT and TN.S grounding systems,
electrical protection: circuit‐breaker (curve D) or fuse (Am) (calibre 16A), with a dedicated 30 mA differential trip
switch (circuit‐breaker or switch),
Acceptable tolerance for tension variation: ‐10%, +7% (while operating).
2.4.2 Connections
the electrical supply cable must not be exposed to elements that are sharp, hot or represent a crush hazard,
check that all cables are secure and all terminal connections are correct,
Use a RO2V electrical supply cable to connect the 11kW appliance,
electrical conduits must be secured,
use the stuffing box to bring the supply cable into the appliance,
loose terminals may cause the supply terminal board to overheat, and will void the warranty,
the appliance must be earthed,
risk of electrical shock inside the device,
only a fully qualified and approved technician should perform cabling connections inside the
appliance,
if the power cable is damaged it must be replaced by a qualified technician.
H04019‐00.A3.EN – 2013/01
ML1_Pac Alpha Ed 01-2013-noir.indd 15
5M
bar
bar
mCE
2.3
m³/h
m³/h
3
m³/h
* minimum distance
by‐pass
filter
water treatment
VE : water inlet valve
VS : water outlet valve
VB : by‐pass valve
7M
6
1.5
2.45
2
4
8
9M
11M
4.95
5
5
5
4
16/01/13 11:05
EN