WARNING: 742 only - Setting days between regeneration to zero will cause
the system to not regenerate. This setting is used for selecting regeneration
on specific days or to use with a remote regeneration input.
• To use the 7-day timer option - see Dealer Installation Manual.
Step 6a: Specific day of week regeneration (742 only)
• To change the controller to regenerate on specific days, set the
number of days between regeneration to zero.
• After this has been completed, the arrow on the left side of the
display will be pointing to Regeneration Time/Day. Press the SET
button and the display will show a flashing cursor at the top under
Sunday. The day of week can be selected when the cursor is
below it.
• To toggle the day on/off, the triangular cursor must be below that
day and flashing.
• The UP and DOWN buttons are used to turn the days flag on/off.
If the cursor is in position but steady on push the SET button to
make the cursor flash.
• To move the cursor when it is steady on, use the UP and DOWN
buttons.
• To move the cursor when it is flashing, push the SET button once.
This will move the cursor one position to the right and change the
status to steady on.
Step 6b: Set Calendar Override (762 Demand Control Only)
• If using 742 control – proceed to step 7.
• Set number of days for calendar override on demand control.
• "0" days is the default for calendar override.
• Days can be adjusted from 1/2 (.5) to 99 days.
• To change, press SET to make the "0" flash.
• Use the UP and DOWN buttons to change to the number of days
desired. Press SET to accept the regen frequency, and advance
to the next cycle.
Step 7: Amount of Regenerant used per Regeneration
If the installation is a filter, skip to Filter Backwash Time. The
amount of regenerant does not apply.
• Select regenerant amount.
• The default setting is 9 lbs of salt per ft3 of resin (110 grams/Liter).
• The 255 and 268 valves will follow the high efficiency settings.
See Table 1