Conduct of luminaire
The motion sensor is faulty
The light sensor is faulty
Dimming value cannot be set
Luminaire turns on by itself
Luminaire does not turn on
Luminaire only turns on
partially (the inner or outer
lamps)
Lamps flicker, luminaire
switches off again after a brief
period of time.
Luminaire cannot be dimmed
6 EN
SensControl Lighting management
If you have any questions about SensControl please contact:
Zumtobel Lighting GmbH
Schweizer Strasse 30
6850 DORNBIRN
AUSTRIA
You can find general information about our products on our website at
www.zumtobel.com or from our competent sales partners. If you have specific
questions, please contact your sales partner.
Possible cause
Dimmed value is set too low, the
luminaire switches off
The room is too bright, the
luminaire switches off
Luminaire is operating in burn-
in mode (status LED flashes
during operation)
The light level in the room is
below the set brightness value
Motion sensor reacts to
movement detected in the
room (also via glass panels)
Motion sensor reacts to a rapid
change in temperature in the
room (possibly caused by air
conditioning or heating
systems)
No power supply
Membrane keyboard is not
connected to SensControl
(connector connection cable)
SensControl unit defective
An electronic ballast is
defective
A lamp is defective (the second
lamp also does not work)
Luminaire is operating in burn-
in mode (status LED flashes
during operation)
The keyboard is defective
Recommendation
p Carry out a factory reset using the
SensControl operating instructions
p Carry out a factory reset using the
SensControl operating instructions
(with TC-L lamps the burn-in process is
stopped and must be restarted)
p Do not interfere with or cover the light
sensor when setting the dimming value
p Check the power supply to the luminaire
p Contact the Service team
p Contact the Service team
p Insert new lamps (note: burn in new lamps
for > 100 hours without dimming)
p Insert new lamps (note: burn in new lamps
for > 100 hours without dimming)