4.2 FUEL HEATING

In order to assure regular ignition and working also at low temperature the burner has an oil pre-heater
fitted in combustion head. The pre-heater starts when thermostats close.
When the required temperature for ignition is reached the thermostat fitted on the nozzle holder starts the
burner. The pre heater remains energised during working and cuts out when burner shuts-down.

4.3 BURNER START-UP CYCLE

Normal
Thermostat
Heating
Motor
Ignition transformer
Valve
Flame
Lock-out lamp
Lock-out due to
failure to shut-down
0
A
Lock out is indicated by a lamp on the control box (3, fig. 1, page 1).
B
In this case the burner will not reset because there is a serious fault.
THE AUTHORIZED SERVICE AGENT WILL FIRST OF ALL CHECK THE EFFICIENCY OF:
Photoresistance (7, fig. 1, page 1).
Pump: interception valve (7), or pressure adjuster piston (5), see fig. 7, page 4.
BURNER CAN BE RESET WITH A PROPER TOOL INSERTED INTO THE HOLE LOCATED AT THE
BOTTOM OF THE CONTROL BOX.
5. MAINTENANCE
Burner requires a periodic maintenance carried out by a qualified and authorized technicians.
Maintenance is essential for the reliability of the burner, avoiding the excessive consumption of fuel and
consequent pollution.
Before carrying out any cleaning or control always first switch off the electrical supply to the
burner acting on the main switch of the system.
Check that there are not obstructions or dents in the supply or return oil pipes.
Clean the filter in the oil suction line and in the pump.
Check for correct fuel consumption.
Replace the nozzle.
Clean the combustion head in the fuel exit area, on the diffuser disc.
Leave the burner working without interruptions for 10 min. and set rightly all the components stated in
this manual. Then carry out a combustion check verifying:
Smoke temperature at the chimney;
Content of CO
( % );
2
Content of CO (ppm);
Smoke value according to opacity smokes index according to Bacharach scale.
2325
Lock-out due to
failure to light
~
150s
12s
0
CALL THE SERVICE AGENT
THE BASIC CHECKS ARE:
A
~
150s
12s
5s
8
GB
Lock-out due to
failure to shut-down
~
0
150s
12s
B
20
60s
D5197